General Data - R410A Heat pump
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
87
M5AC020CR M5AC025CR
Btu/h
17000 21000
W 4980 6150
Btu/h 21500 25000
W 6300 7330
COOLING W
2550 2760
HEATING W 2590 2790
COOLING A 11.9 12.7
HEATING A
12.1 12.9
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 125 / 276 165 / 364
dBA
57 57
COOLING
l/s / m
3
/hr
0.23 / 0.84 0.28 / 1.00
HEATING
l/s / m
3
/hr
0.32 / 1.16 0.35 / 1.25
11
MAX. WATER OPER. PRESSURE kPa / psi
COOLING
l/s / m
3
/hr
0.23 / 0.84 0.28 / 1.00
HEATING
l/s / m
3
/hr
0.32 / 1.16 0.35 / 1.25
INSTALLATION PIPE CONNECITON mm/in
COOLING m 9.7 10.1
HEATING m
7.3 9.1
L / ft
3
ROTARY ROTARY
0 - 100% 0 - 100%
kg/lb 1.2 / 2.7 1.7 / 3.8
HIGH HEAD CIRCULATOR
22 / 0.78
460 / 18.1
958 / 37.7
1309 / 51.5
574 / 22.6
NOMINAL TOTAL INPUT POWER
HYDRAULIC KIT
PUMP
SOUND PRESSURE LEVEL
EVAPORATOR
CONDENSER FAN
TYPE
NOMINAL WATER FLOW
PROPELLER / DIRECT
WATER FLOW RATE
MATERIAL
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
UNIT DIMENSION
PACKING DIMENSION
UNIT WEIGHT
TANK
PIPING
REFRIGERANT
CHARGING MASS
STAGE OF CAPACITY CONTROL (Btu/h)
TYPE
CAPACITY/VOLUME
MILD STEEL COATED WITH ZINC
HEAD
COMPRESSOR
NOMINAL RUNNING CURRENT
R410A
1000 / 145
25.4 / 1
POWER SOURCE
CONTROL CAPILLARY TUBE
220-240 / 1 / 50
800 / 31.5
1160 / 45.7
Comentarios a estos manuales