8. Appendix
SENSOR Type Unit Default Min Max Resolution
S1 Entering water sensor calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S2 Leaving water sensor calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S3 Air sensor calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S4 Defrost(condenser) sensor 1 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S5 Defrost(condenser) sensor 2 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S6 Defrost(condenser) sensor 3 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S7 Defrost(condenser) sensor 4 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S8 Compressor discharge sensor 1 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S9 Compressor discharge sensor 2 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S10 Compressor discharge sensor 3 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
S11 Compressor discharge sensor 4 calibration U °C (F) 0 (0) -12 (21.6) -12 (21.6) 0.1
General Type Unit Default Min Max Resolution
Model F Flag 4 0 2 1
0=Chiller (Chiller+Boiler)
1=Heat pump,
2=Chiller/ Boiler,
3=Heat pump/ Boiler, 4=Chiller+Boiler
5=Heat pump+Boiller
Number of compressor F Flag 1 1 4 1
1=1 compressor,
2=2 compressor,
3=3 compressor,
4=4 compressor
On/Off input F Flag 0 (disable) 0 1 1
0=disable, 1=enable
Coo/ Heat input F Flag 0 (disable) 0 1 1
0=disable, 1=enable
External alarm input F Flag 0 (disable) 0 1 1
0=disable, 1=enable
Water system for chiller network F Flag 0 (disable) 0 1 1
0=independent, 1=modular
G7 Unit number F Flag 0 0 50 1
G5
G6
G1
G2
G3
G4
REGULATOR Type Unit Default Min Max Resolution
R1 Cooling set-point D °C (F) 12 (53.6) R5 R6 0.1
R2 Cooling differential U °C (F) 1.5* (2.7) 0.4 (0.7) 10 (18) 0.1
R3 Heating set-point D °C (F) 40 (104) R7 R8 0.1
R4 Heating differential U °C (F) 1.5* (2.7) 0.4 (0.7) 10 (18) 0.1
R5 Minimum Cooling set-point U °C (F) 7 (44.6) -20 (-4) R6 1
R6 Maximum Cooling set-point U °C (F) 20 (68) R5 40 (104) 1
R7 Minimum Heating set-point U °C (F) 30 (68) -20 (-4) R8 1
R8 Maximum Heating set-point U °C (F) 50 (122) R7 90 (194) 1
R9 Auxiliary heater set-point(threshold below U °C (F) 5 (9) 0 (0) 40 (72) 0.1
below heating set-point)
R10 Auxiliary heater differential U °C (F) 2 (3.6) 0.4 (0.7) 10 (18) 0.1
R11 Auto boiler set-point(threshold below U °C (F) 5 (9) 0 (0) 40 (72) 0.1
Heating set-point)
R12 Auto boiler differential U °C (F) 2 (3.6) 0.4 (0.7) 10 (18) 0.1
R13 Auto boiler start time threshold U min 30 0 199 1
COMPRESSOR Type Unit Default Max Min Resolution
C1 Compressor minimum run time U sec 120 0 1990 10
C2 Compressor minimum stop time U sec 180 0 1990 10
C3 Time interval between two starts U sec 450 0 1990 10
C4 Start delay between two compressors U sec 15 0 199 1
C5 Pump on ? compressor on delay U sec 180 0 1990 10
C6 Comp off ? pump off delay U sec 60 0 199 10
C7 Discharge cut-off-set-point U °C (F) 120(248) 0 (32) 150 (302) 1
CONDENSSOR Type Unit Default Max Min Resolution
D1 Start defrost temperature U °C (F) 0 (32) -20 (-4) D2 1
D2 End defrost temperature U °C (F) 14 (57) D1 40 (104) 1
D3 Maximum duration of defrost cycle U min 10 1 40 1
D4 Defrost interval time U min 45 0 199 1
D5 Delay before defrosting U sec 0 0 1990 10
D6 Delay after defrosting U sec 120 0 1990 10