General Data - R22 Cooling only
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
69
MAC050C MAC060C
Btu/h
50000 53000
W 14654 15533
W 5245 6361
A 9.3 12.3
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 196 / 432 203 / 448
dBA
60 61
l/s / m
3
/hr
0.70 / 2.5 0.74 / 2.7
22
MAX. WATER OPER. PRESSURE kPa / psi
l/s / m
3
/hr
0.70 / 2.5 0.74 / 2.7
INSTALLATION PIPE CONNECITON mm/in
m 7.5 8.3
L / ft
3
SCROLL SCROLL
0 - 100% 0 - 100%
kg/lb
3.1 / 6.8 3.1 / 6.8
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
REFRIGERANT TYPE
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
SOUND PRESSURE LEVEL
574 / 22.6
PROPELLER / DIRECT
380-415 / 3 / 50
HORIZONTAL MULTISTAGE END-SUCTION
EVAPORATOR
PUMP
WATER FLOW RATE
40 / 1.41
CONDENSER FAN
POWER SOURCE
CONTROL
NOMINAL WATER FLOW
1410 / 55.5
1160 / 45.7
460 / 18.1
1578 / 62.1
1309 / 51.5
CHARGING MASS
R22
1000 / 145
25.4 / 1
CAPILLARY TUBE
UNIT DIMENSION
PACKING DIMENSION
UNIT WEIGHT
HYDRAULIC KIT
STAGE OF CAPACITY CONTROL (Btu/h)
PIPING
HEAD
TYPE
REFRIGERANT
COMPRESSOR
MATERIAL
TANK
TYPE
CAPACITY/VOLUME
MILD STEEL COATED WITH ZINC