McQuay MAC Especificaciones Pagina 118

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 180
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 117
Safety Devices - R407C Cooling only & Heat pump
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
116
M4AC080C/CR M4AC100C/CR
NC NC
OPEN kPa / psi 3243 / 470 3243 / 470
CLOSE kPa / psi 2650 / 384 2650 / 384
NC NC
OPEN kPa / psi 124 / 18 124 / 18
CLOSE kPa / psi 193 / 28 193 / 28
NC NC
OPEN kPa / psi
48 / 7 48 / 7
CLOSE kPa / psi 152 / 22 152 / 22
BUILT IN ON BOARD BUILT IN ON BOARD
DIFFERENTIAL PRESSURE SWITCH YES YES
ANTI-FREEZE PROTECTION SENSOR
YES YES
DISCH. THERMOSTAT SETTING °C / °F 110 / 230 110 / 230
OVER PRESSURE RELIEF VALVE YES YES
ANTI-FREEZE HEATER ON BPHE
YES YES
YES YES
YES YES
M4AC120C/CR M4AC150C/CR
NC NC
OPEN kPa / psi 3243 / 470 3243 / 470
CLOSE kPa / psi 2650 / 384 2650 / 384
NC NC
OPEN kPa / psi 124 / 18 124 / 18
CLOSE kPa / psi 193 / 28 193 / 28
NC NC
OPEN kPa / psi 48 / 7 48 / 7
CLOSE kPa / psi 152 / 22 152 / 22
BUILT IN ON BOARD BUILT IN ON BOARD
DIFFERENTIAL PRESSURE SWITCH
YES YES
ANTI-FREEZE PROTECTION SENSOR YES YES
DISCH. THERMOSTAT SETTING °C / °F 110 / 230 110 / 230
OVER PRESSURE RELIEF VALVE YES YES
ANTI-FREEZE HEATER ON BPHE
YES YES
YES YES
YES YES
PHASE PROTECTION
MODEL
SAFETY DEVICE
COMPRESSOR OLP
PHASE PROTECTION
HIGH PRESSURE
SWITCH
LOW PRESSURE
SWITCH (COOLING
ONLY)
PUMP OLP
TYPE
TYPE
TYPE
LOW PRESSURE
SWITCH (HEAT
PUMP)
MODEL
SAFETY DEVICE
HIGH PRESSURE
SWITCH
TYPE
PUMP OLP
COMPRESSOR OLP
LOW PRESSURE
SWITCH (HEAT
PUMP)
TYPE
LOW PRESSURE
SWITCH (COOLING
ONLY)
TYPE
Vista de pagina 117
1 2 ... 113 114 115 116 117 118 119 120 121 122 123 ... 179 180

Comentarios a estos manuales