4.2 Others Configuration
• JH2 in chiller panel should let it open (put the jumper header on one pin only) all the time
unless user need to do CMOS reset to that p
articular panel.
• JH3 should let it open (put the jumper header on one pin only) all the time as well.
• Remember to put in the coin cell battery on the panel. Without the backup battery
, the panel will
always reset the time to 12:00am, 1st Jan 2000.
4.3 Installation of the Chiller Panel Controller
• Disconnect the unit and ensure no others unit energy source that supplies the panel.
• Open the rear panel of the Chiller Panel (insert a ‘flat-head’ screwdriver in the top joint of main
casing with rear panel to open the real panel).
• Pass the necessary wires of the panel across the large opening in the rear p
anel. Place the rear
panel flat support against the wall and make marks on the wall through the four installation holes
(inner and outer).
• Drill four appropriate holes in the marked places.
• Attach the rear panel to the wall and put on the screws on it. Ensure that all cables are passed
through the hole of the rear panel.
• Connect the wires to the corresponding terminal according to the wiring bus network. The
power supply and communication wires must be correctly connected to ensure that the
panel works.
• Close the chiller panel (ensure the bottom joint is aligned for the casing, then complete others joint
p
art. Ensure that the contacts at the back of the panel are aligned with each others).
Bus Wiring Diagram
15
Comentarios a estos manuales