Electrical Data - R407C Heat pump
M4AC020CR M4AC025CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
135 135
RATED RUNNING CURRENT A
0.67 0.67
MOTOR OUTPUT W
145 145
66
EF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR
µF
50 50
RATED INPUT POWER (COOLING) W
2289 2755
RATED INPUT POWER (HEATING) W
2369 2415
RATED RUNNING CURRENT (COOLING) A
11.20 12.80
RATED RUNNING CURRENT (HEATING) A
11.50 12.60
LOCKED ROTOR AMP. A
58 82
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER (COOLING) W
173 186
RATED INPUT POWER (HEATING) W
181 195
RATED RUNNING CURRENT (COOLING) A
0.76 0.82
RATED RUNNING CURRENT (HEATING) A
0.79 0.86
M4AC030CR M4AC040CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
135 270
RATED RUNNING CURRENT A
0.67 1.34
MOTOR OUTPUT W
145 145 x2
66
NA NA
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 380 - 415 / 3 / 50
CAPACITOR
µF
60 NA
RATED INPUT POWER (COOLING) W
3475 4230
RATED INPUT POWER (HEATING) W
3655 4390
RATED RUNNING CURRENT (COOLING) A
17.7 7.9
RATED RUNNING CURRENT (HEATING) A
18.4 8.0
LOCKED ROTOR AMP. A
114 66
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 380 - 415 / 3 / 50
RATED INPUT POWER (COOLING) W
194 320
RATED INPUT POWER (HEATING) W
214 334
RATED RUNNING CURRENT (COOLING) A
0.85 0.71
RATED RUNNING CURRENT (HEATING) A
0.94 0.74
M4AC050CR M4AC060CR
FF
POWER SOURCE V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W
270 270
RATED RUNNING CURRENT A
1.34 1.34
MOTOR OUTPUT W
145 x2 145 x2
66
NA NA
POWER SOURCE V/Ph/Hz
380 - 415 / 3 / 50 380 - 415 / 3 / 50
CAPACITOR µ
F
NA NA
RATED INPUT POWER (COOLING) W
4840 5890
RATED INPUT POWER (HEATING) W
5030 5640
RATED RUNNING CURRENT (COOLING) A
8.3 11.5
RATED RUNNING CURRENT (HEATING) A
8.6 11.4
LOCKED ROTOR AMP. A
74 101
FF
POWER SOURCE V/Ph/Hz
380 - 415 / 3 / 50 380 - 415 / 3 / 50
RATED INPUT POWER (COOLING) W
336 347
RATED INPUT POWER (HEATING) W
347 358
RATED RUNNING CURRENT (COOLING) A
0.75 0.77
RATED RUNNING CURRENT (HEATING) A
0.77 0.79
COMPRESSOR
INSULATION GRADE
WATER PUMP
INSULATION GRADE
MODEL
CONDENSER FAN
MOTOR
INSULATION GRADE
POLES
COMPRESSOR
INSULATION GRADE
WATER PUMP
INSULATION GRADE
MODEL
CONDENSER FAN
MOTOR
INSULATION GRADE
POLES
MODEL
INSULATION GRADE
INSULATION GRADE
CONDENSER FAN
MOTOR
POLES
INSULATION GRADE
COMPRESSOR
WATER PUMP
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
142