General Data - R22 Heat pump
76
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
MAC120CR MAC150CR
Btu/h
113000 138000
W 33118 40445
Btu/h 120000 132000
W 35169 38686
COOLING W
11714 13881
HEATING W 11948 14572
COOLING A 23.7 26.3
HEATING A
23.8 27.3
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb 480 / 1058 560 / 1235
dBA
67 69
COOLING
l/s / m
3
/hr
1.67 / 6.0 2.00 / 7.2
HEATING
l/s / m
3
/hr
1.79 / 6.4 2.10 / 7.6
22
MAX. WATER OPER. PRESSURE kPa / psi
COOLING
l/s / m
3
/hr
1.67 / 6.0 2.00 / 7.2
HEATING
l/s / m
3
/hr
1.79 / 6.4 2.10 / 7.6
INSTALLATION PIPE CONNECITON mm/in
COOLING m 19.7 16.5
HEATING m
18.4 17.4
L / ft
3
SCROLL SCROLL
0 - 50 - 100% 0 - 50 - 100%
kg/lb 7.6 x2 / 16.8 x2 6.5 x2 / 14.3 x2
NOMINAL RUNNING CURRENT
R22
1000 / 145
42 / 1 1/4"
POWER SOURCE
CONTROL CAPILLARY TUBE
380-415 / 3 / 50
1245 / 49.0
1800 / 70.9
TANK
PIPING
REFRIGERANT
CHARGING MASS
STAGE OF CAPACITY CONTROL (Btu/h)
TYPE
CAPACITY/VOLUME
NA
HEAD
COMPRESSOR
MATERIAL
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
UNIT DIMENSION
PACKING DIMENSION
UNIT WEIGHT
NOMINAL TOTAL INPUT POWER
HYDRAULIC KIT
PUMP
SOUND PRESSURE LEVEL
EVAPORATOR
CONDENSER FAN
TYPE
NOMINAL WATER FLOW
PROPELLER / DIRECT
WATER FLOW RATE
HORIZONTAL MULTISTAGE END-SUCTION
NA
1150 / 45.3
1452 / 57.2
2032 / 80.0
1282 / 50.5