Additional Charge
The pre-charged of R410A in the Water Source Heat Pump unit is suitable for standard pipe of length
up:-
a) 2 meter for M5WSS007/010/015/016/020/025/030/040/050AR
b) 5 meter for M5WSS060AR
c) 5 meter for M5WST 040/050/060AR
When the piping is more than the above stated standard pipe length, kindly add additional charge
referring to the table below.
Models gram/meter
M5WSS007AR
18.5
M5WSS010AR
18.5
M5WSS015AR
18.5
M5WSS016AR
18.5
M5WSS020AR
18.5
M5WSS025AR
18.5
M5WSS030AR
18.5
M5WSS040AR
47.5
M5WSS050AR
47.5
M5WSS060AR
47.5
M5WSS007AR M5WSS010AR M5WSS015AR M5WSS016AR M5WSS020AR
Max Length, L 12 m 12 m 12 m 12 m 12 m
Max. Elevation, H 5 m 5 m 5 m 5 m 5 m
Max. No. of bends 10 10 10 10 10
Liquid Valve Size 6.35mm (1/4”) 6.35mm (1/4”) 6.35mm (1/4”) 6.35mm (1/4”) 6.35mm (1/4”)
Gas Valve Size 9.52mm (3/8”) 9.52mm (3/8”) 12.7mm (1/2”) 12.7mm (1/2”) 12.7mm (1/2”)
M5WSS025AR M5WSS030AR M5WSS040AR M5WSS050AR M5WSS060AR
Max Len
th, L 12 m 12 m 35m 35m 35m
Max. Elevation, H 5 m 5 m 10m 10m 10m
Max. No. of bends 10 10 10 10 10
Liquid Valve Size 6.35mm (1/4”) 9.52mm (3/8”) 9.52mm (3/8”) 9.52mm (3/8”) 9.52mm (3/8”)
Gas Valve Size 15.88mm (5/8”) 15.88mm (5/8”) 15.88mm (5/8”) 15.88mm (5/8”) 19.05mm (3/4”)
Models gram/meter
M5WST040AR
47.5
M5WST050AR
47.5
M5WST060AR
47.5
M5WST040AR M5WST050AR M5WST060AR
Max Length, L 35m 35m 35m
Max. Elevation, H 10m 10m 10m
Max. No. of bends 10 10 10
Liquid Valve Size 9.52mm (3/8”) 9.52mm (3/8”) 9.52mm (3/8”)
Gas Valve Size 15.88mm (5/8”) 15.88mm (5/8”) 19.05mm (3/4”)
35