M5CCWS020CR/M5WSS020AR
Heating mode (Heatpump)
Water Flow Rate = 0.75 m
3
/hr
Water Flow Rate = 1.25 m
3
/hr
Water Flow Rate = 1.75 m
3
/hr
Note:
1. TC = Total Capacity, EWT = Entering Water Temperature
2. All datas above are generated at delta T = Entering Water Temperature - Leaving Water Temperature = 5
°C
139
EWT Capacity
(°C) (kW) 15 17 19 20 22 24 27 30
10
TC
5.31 5.20 5.10 5.04 4.94 4.84 4.69 4.54
12
TC
5.57 5.47 5.36 5.31 5.20 5.10 4.94 4.78
15
TC
5.97 5.87 5.76 5.70 5.60 5.48 5.31 5.14
20
TC
6.64 6.53 6.42 6.36 6.25 6.13 5.93 5.74
25
TC
7.17 7.05 6.93 6.86 6.74 6.60 6.38 6.17
30
TC
7.70 7.56 7.43 7.36 7.23 7.07 6.83 6.59
32
TC
7.91 7.77 7.63 7.56 7.43 7.26 7.01 6.76
35
TC
8.22 8.08 7.94 7.86 7.72 7.54 7.28 7.01
EWT Capacity
(°C) (kW) 15 17 19 20 22 24 27 30
10
TC
5.62 5.51 5.40 5.34 5.23 5.12 4.96 4.80
12
TC
5.90 5.79 5.68 5.62 5.51 5.40 5.23 5.06
15
TC
6.33 6.21 6.10 6.04 5.93 5.81 5.62 5.44
20
TC
7.03 6.92 6.80 6.74 6.62 6.49 6.28 6.08
25
TC
7.59 7.46 7.33 7.27 7.14 6.99 6.76 6.53
30
TC
8.15 8.01 7.87 7.80 7.66 7.49 7.23 6.98
32
TC
8.37 8.23 8.08 8.01 7.86 7.69 7.42 7.15
35
TC
8.71 8.56 8.40 8.33 8.18 7.99 7.71 7.42
EWT Capacity
(°C) (kW) 15 17 19 20 22 24 27 30
10
TC
5.85 5.74 5.62 5.56 5.45 5.34 5.17 5.00
12
TC
6.15 6.03 5.91 5.85 5.74 5.62 5.45 5.27
15
TC
6.59 6.47 6.35 6.29 6.17 6.05 5.86 5.67
20
TC
7.33 7.21 7.08 7.02 6.90 6.76 6.55 6.34
25
TC
7.91 7.77 7.64 7.57 7.44 7.28 7.04 6.80
30
TC
8.49 8.34 8.20 8.12 7.98 7.80 7.53 7.27
32
TC
8.72 8.57 8.42 8.34 8.19 8.01 7.73 7.45
35
TC
9.07 8.91 8.75 8.68 8.52 8.32 8.03 7.73