M5CCWS040CR/M5WSS040AR
Cooling Only/ Cooling Mode (Heatpump)
Water Flow Rate = 1.26 m
3
/hr
Water Flow Rate = 2.10 m
3
/hr
Water Flow Rate = 2.94 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 11.47 10.98 10.63 10.27 9.71 9.14 8.57
SC
11.23 10.77 10.45 10.12 9.60 9.08 8.56
TC 11.91 11.38 11.00 10.62 9.99 9.36 8.73
SC 10.29 9.94 9.70 9.46 9.07 8.69 8.31
TC
12.48 11.90 11.49 11.07 10.36 9.65 8.93
SC 9.04 8.83 8.69 7.97 8.35 8.15 7.97
TC
12.62 12.11 11.74 11.37 10.70 10.02 9.35
SC 8.29 8.10 7.96 7.84 7.65 7.47 7.29
TC
13.04 12.71 12.48 12.25 11.70 11.16 10.61
SC 6.11 5.99 5.91 5.82 5.66 5.51 5.35
TC 13.18 12.92 12.73 12.54 12.04 11.54 11.03
SC
5.41 5.32 5.25 5.18 5.03 4.88 4.73
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 12.00 11.48 11.11 10.74 10.15 9.56 8.97
SC 11.74 11.26 10.92 10.58 10.04 9.50 8.95
TC
12.45 11.90 11.50 11.10 10.44 9.79 9.13
SC 10.76 10.40 10.14 9.89 9.49 9.09 8.69
TC
13.05 12.45 12.01 11.58 10.83 10.09 9.34
SC 9.45 9.24 9.09 8.34 8.73 8.53 8.33
TC 13.20 12.66 12.27 11.89 11.18 10.48 9.78
SC 8.67 8.47 8.33 8.19 8.00 7.81 7.63
TC 13.64 13.30 13.05 12.81 12.24 11.67 11.10
SC
6.39 6.27 6.17 6.08 5.92 5.76 5.60
TC 13.78 13.51 13.31 13.11 12.59 12.06 11.54
SC
5.66 5.56 5.49 5.42 5.26 5.10 4.94
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 30 35 40 45
TC
12.26 11.73 11.35 10.98 10.37 9.77 9.16
SC 12.00 11.51 11.16 10.81 10.26 9.70 9.15
TC
12.72 12.15 11.75 11.34 10.67 10.00 9.32
SC 10.99 10.62 10.36 10.11 9.69 9.28 8.88
TC 13.33 12.71 12.27 11.83 11.07 10.31 9.54
SC 9.66 9.43 9.28 8.52 8.92 8.71 8.51
TC 13.48 12.93 12.54 12.14 11.43 10.71 9.99
SC
8.85 8.65 8.51 8.37 8.17 7.98 7.79
TC 13.93 13.58 13.33 13.08 12.50 11.92 11.34
SC
6.53 6.40 6.31 6.22 6.05 5.88 5.72
TC 14.08 13.80 13.60 13.40 12.86 12.32 11.79
SC 5.78 5.68 5.61 5.54 5.37 5.21 5.05
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
23
24
15.5
17
19
20
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5
°C
112