R410A Refrigerant Piping
Copper Pipe Connection
Do not use contaminated, dented or used copper tubing. Do not use mineral oil on flare part. It is necessary
to use proper copper tubing for safety reasons as R410A has a higher pressure than R22 or R407C. Do not
use copper tubes with less than 0.8 mm thickness. All piping connections are by the method of flaring.
Install a bi-flow (two ways) filter drier at the liquid line to absorb unwanted moisture in the system. R410A
compressor uses POE oil as lubricant which is very hygroscopic and hydrolysis may occur that will generate
acid when mix with moisture or water.
Flare Work
Use either a flare tool specially for R410A or a conventional type. Head projection dimension may differ
according to type of flare tool. Refer to table below:
Diameter A(mm)
in mm Clutch Type
For R410A
Conventional
Clutch Type
1/4 6.35 0-0.5 0.7-1.3
3/8 9.52 0-0.5 0.7-1.3
1/2 12.7 0-0.5 0.7-1.3
5/8 15.88 0-0.5 0.7-1.3
3/4 19.05 0-0.5 0.7-1.3
Flare end diameter is also different for R410A. Flare section should be uniform or even. Crack on the flare
section or burr on the flare edge is not acceptable. Make new flare tubing again to prevent potential gas
leak.
Diameter D Flare End Diameter
in mm
1/4 6.35 9.1
3/8 9.52 13.2
1/2 12.7 16.6
5/8 15.88 19.7
3/4 19.05 24.0
32