Water Flow Rate = 0.45 m
3
/hr
Water Flow Rate = 0.75 m
3
/hr
Water Flow Rate = 1.05 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 3.63 3.47 3.36 3.25 3.07 2.89 2.71
SC 3.55 3.40 3.30 3.20 3.03 2.87 2.71
TC
3.76 3.60 3.48 3.36 3.16 2.96 2.76
SC 3.25 3.14 3.07 2.99 2.87 2.75 2.63
TC
3.94 3.76 3.63 3.50 3.27 3.05 2.82
SC 2.86 2.79 2.75 3.01 2.64 2.58 2.52
TC 3.99 3.83 3.71 3.59 3.38 3.17 2.96
SC
2.62 2.56 2.52 2.48 2.42 2.36 2.31
TC 4.12 4.02 3.94 3.87 3.70 3.53 3.35
SC
1.93 1.89 1.87 1.84 1.79 1.74 1.69
TC 4.17 4.08 4.02 3.96 3.80 3.65 3.49
SC
1.71 1.68 1.66 1.64 1.59 1.54 1.49
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC
3.79 3.63 3.51 3.40 3.21 3.02 2.83
SC 3.71 3.56 3.45 3.34 3.17 3.00 2.83
TC 3.94 3.76 3.63 3.51 3.30 3.09 2.88
SC
3.40 3.29 3.21 3.13 3.00 2.87 2.75
TC 4.13 3.93 3.80 3.66 3.42 3.19 2.95
SC
2.99 2.92 2.87 3.15 2.76 2.69 2.63
TC 4.17 4.00 3.88 3.76 3.54 3.31 3.09
SC 2.74 2.68 2.63 2.59 2.53 2.47 2.41
TC
4.31 4.20 4.12 4.05 3.87 3.69 3.51
SC 2.02 1.98 1.95 1.92 1.87 1.82 1.77
TC
4.36 4.27 4.21 4.14 3.98 3.81 3.65
SC 1.79 1.76 1.74 1.71 1.66 1.61 1.56
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 3.87 3.71 3.59 3.47 3.28 3.09 2.90
SC 3.79 3.64 3.53 3.42 3.24 3.07 2.89
TC
4.02 3.84 3.71 3.58 3.37 3.16 2.95
SC 3.47 3.36 3.28 3.19 3.06 2.93 2.81
TC
4.21 4.02 3.88 3.74 3.50 3.26 3.02
SC 3.05 2.98 2.93 3.22 2.82 2.75 2.69
TC 4.26 4.09 3.96 3.84 3.61 3.38 3.16
SC
2.80 2.73 2.69 2.65 2.58 2.52 2.46
TC 4.40 4.29 4.21 4.14 3.95 3.77 3.58
SC
2.06 2.02 1.99 1.96 1.91 1.86 1.81
TC 4.45 4.36 4.30 4.23 4.06 3.90 3.73
SC 1.83 1.80 1.77 1.75 1.70 1.65 1.60
23
24
15.5
17
19
20
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5