Vista de pagina 20
Wired Remote Control
Cooling / Heatpump Model
Error Code at 7 Segment Display Operation / Faulty Indication
Blink E1 Room sensor contact loose / short
Blink E2 Indoor coil sensor contact loose / short
Blink E3 Outdoor coil sensor contact loose / short
Blink E4 Compressor overload
Blink E5 Gas leak
Blink E6 Pump faulty
Blink Heat LED Outdoor defrost (for Heatpump only)
Water Pump
The water pump will on if compressor is on during cooling cycle. The pump will remain on for at least 5
minutes after the compressor is off.
During mode change from cooling to non-cooling mode, the pump will on for minimum 5 minutes. During
defrost cycle, the pump will on and will on for another 5 minutes once the defrost cycle is terminated.
Water Level Switch
This normally close switch is to detect faults in water pump system. It will confirm for 30 seconds for switch
open and 60 seconds for switch close.
Once switch is confirmed open, it will force compressor to cut off. If the switch is closed within 5 minutes, the
compressor is allowed to cut in. If the switch does not close for more than 5 minutes, the system will warn
user regarding the fault, the compressor is not allowed to cut in. If the switch is confirmed opened twice
within 30 minutes, the system assumes there are faults.