52
MVCU-2009 Engineering & Physical Data
Safety Devices
MODEL
INDOOR UNIT
MWM025G MWM030F
OUTDOOR UNIT
MVCU025A MVCU030A
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
N/A NC
OPEN kPa / psi
N/A 2940
CLOSE kPa / psi
N/A 2410
LOW PRESSURE SWITCH
TYPE
N/A NC
OPEN kPa / psi
N/A 124
CLOSE kPa / psi
N/A 193
PHASE SEQUENCER
N/A N/A
DISCHARGE THERMOSTAT SETTING °C / °F
N/A N/A
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
MODEL
INDOOR UNIT
MCM025D MCM030D
OUTDOOR UNIT
MVCU025A MVCU030A
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
N/A NC
OPEN kPa / psi
N/A 2940
CLOSE kPa / psi
N/A 2410
LOW PRESSURE SWITCH
TYPE
N/A NC
OPEN kPa / psi
N/A 124
CLOSE kPa / psi
N/A 193
PHASE SEQUENCER
N/A N/A
DISCHARGE THERMOSTAT SETTING °C / °F
N/A N/A
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
MODEL
INDOOR UNIT
MCM040D MCM040D
OUTDOOR UNIT
MVCU035A MVCU040A
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
NC NC
OPEN kPa / psi
2940 2940
CLOSE kPa / psi
2410 2410
LOW PRESSURE SWITCH
TYPE
NC NC
OPEN kPa / psi
124 124
CLOSE kPa / psi
193 193
PHASE SEQUENCER
N/A N/A
DISCHARGE THERMOSTAT SETTING °C / °F
N/A N/A
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
MODEL
INDOOR UNIT
MCM050D MCM062C
OUTDOOR UNIT
MVCU050A MVCU060A
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
NC NC
OPEN kPa / psi
2940 2940
CLOSE kPa / psi
2410 2410
LOW PRESSURE SWITCH
TYPE
NC NC
OPEN kPa / psi
124 124
CLOSE kPa / psi
193 193
PHASE SEQUENCER
N/A N/A
DISCHARGE THERMOSTAT SETTING °C / °F
N/A N/A
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
07_General data.indd 5207_General data.indd 52 4/28/2009 11:20:52 AM4/28/2009 11:20:52 AM