34
MVCU-2009 Engineering & Physical Data
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT MCM040D MCM040D
OUTDOOR UNIT MVCU035A MVCU040A
NOMINAL CAPACITY
Btu/h 35000 40000
W 10258 11723
NOMINAL TOTAL INPUT POWER W 3390 3220
NOMINAL RUNNING CURRENT A 5.9 5.8
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
EER W/W 3.03 3.64
REFRIGERANT TYPE R22 R22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
AUTO LOUVER (UP & DOWN)
& MANUAL LOUVER (BOTTOM)
AUTO LOUVER (UP & DOWN)
& MANUAL LOUVER (BOTTOM)
OPERATION
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 477 / 1010 477 / 1010
MEDIUM l/s / CFM 420 / 890 420 / 890
LOW l/s / CFM 368 / 780 368 / 780
EXTERNAL STATIC PRESSURE (H/M/L) Pa / in.wg. --
SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 52 54 / 53 / 52
UNIT DIMENSION
HEIGHT mm/in 249 / 9.8 249 / 9.8
WIDTH mm/in 1714 / 67.4 1714 / 67.4
DEPTH mm/in 670 / 26.3 670 / 26.3
PACKING DIMENSION
HEIGHT mm/in 345 / 13.6 345 / 13.6
WIDTH mm/in 1816 / 71.4 1816 / 71.4
DEPTH mm/in 760 / 29.9 760 / 29.9
UNIT WEIGHT kg/lb 70 / 154 70 / 154
CONDENSATE DRAIN SIZE
mm/in
19 / 3/4 19 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 1338 / 2836 1567 / 3320
SOUND PRESSURE LEVEL dBA 64 67
UNIT DIMENSION
HEIGHT mm/in 841 / 33.1 984 / 38.7
WIDTH mm/in 572 / 22.5 762 / 30.0
DEPTH mm/in 572 / 22.5 762 / 30.0
PACKING DIMENSION
HEIGHT
mm/in
950 / 37.4 1090 / 42.9
WIDTH mm/in 660 / 26.0 860 / 33.9
DEPTH mm/in 660 / 26.0 860 / 33.9
UNIT WEIGHT kg/lb 70 / 154 93 / 205
PIPE CONNECTION
TYPE BRAZED VALVE BRAZED VALVE
SIZE
LIQUID mm/in 9.5 / 3/8 9.5 / 3/8
GAS mm/in 15.9 / 5/8 19 / 3/4
REFRIGERANT CHARGE kg/lb 2.8 / 6.1 3.5 / 7.7
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
07_General data.indd 3407_General data.indd 34 4/28/2009 11:20:46 AM4/28/2009 11:20:46 AM