15
Application Information MVCU-2009
Installation of Outdoor Unit
The unit should be installed in accordance with all national and local codes and regulations which govern
the installation of this type of equipment.
The VCU unit must not be installed with any duct work on the air discharge side. The outdoor fan is a
propeller type and is not designed to operate against any additional external static.
The maximum and minimum operating conditions must be observed to assure the system to maximize the
capacity with minimum service. Please refer to “Operating Range”.
Installation Clearance
Outdoor units must be installed such that there is no short circuit of the hot discharge air to obstruction to
smooth air fl ow.
Please allow 610 mm clearance between units for proper air fl ow.
MODEL A B C D
All VCUs 305 mm 305 mm 1219 mm 762 mm
Wiring
Electrical Connections
Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL
ELECTRICAL CODES for fi eld wiring rules. Be sure that installations comply with the rules and regulations.
General Precautions
Ensure that the rated voltage of the unit corresponds to the name plate before carrying out proper wiring
according to the wiring diagram.
Provide a power outlet to be used exclusively for each unit. A power supply disconnects and a circuit
breaker for over-current protection should be provided in the exclusive line.
The unit must be GROUNDED to prevent possible hazards due to insulation failures.
All wiring must be fi rmly connected.
All wiring must not touch the hot refrigerant piping, compressor or any moving parts of fan motors.
•
•
•
•
•
•
•
•
•
•