McQuay MCK050A Especificaciones Pagina 42

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 130
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 41
40
MVCU-2009 Engineering & Physical Data
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT MCC040C MCC040C
OUTDOOR UNIT MVCU035A MVCU040A
NOMINAL CAPACITY
Btu/h 36000 40000
W 10551 11723
NOMINAL TOTAL INPUT POWER W 3685 3504
NOMINAL RUNNING CURRENT A 6.4 6.2
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
EER W/W 3.11 3.65
REFRIGERANT TYPE R22 R22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE DUCTED DUCTED
OPERATION SLM WIRED HANDSET SLM WIRED HANDSET
AIR FLOW
SUPER HIGH l/s / CFM 519 / 1100 519 / 1100
HIGH l/s / CFM 500 / 1060 500 / 1060
MEDIUM l/s / CFM 467 / 990 467 / 990
LOW l/s / CFM 425 / 900 425 / 900
EXTERNAL STATIC PRESSURE (SH/H/M/L) Pa / in.wg.
206 / 176 / 127 / 93 (0.8 / 0.7 / 0.5
/ 0.4)
206 / 176 / 127 / 93 (0.8 / 0.7 / 0.5
/ 0.4)
SOUND PRESSURE LEVEL (SH/H/M/L) dBA 51 / 49 / 45 / 41 51 / 49 / 45 / 41
UNIT DIMENSION
HEIGHT mm/in 378 / 14.9 378 / 14.9
WIDTH mm/in 1045 / 41.1 1045 / 41.1
DEPTH mm/in 541 / 21.3 541 / 21.3
PACKING DIMENSION
HEIGHT mm/in 415 / 16.3 415 / 16.3
WIDTH mm/in 1245 / 49.0 1245 / 49.0
DEPTH mm/in 631 / 24.8 631 / 24.8
UNIT WEIGHT kg/lb 42 / 93 42 / 93
CONDENSATE DRAIN SIZE
mm/in
19 / 3/4 19 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 1338 / 2836 1567 / 3320
SOUND PRESSURE LEVEL dBA 64 67
UNIT DIMENSION
HEIGHT mm/in 841 / 33.1 984 / 38.7
WIDTH mm/in 572 / 22.5 762 / 30.0
DEPTH mm/in 572 / 22.5 762 / 30.0
PACKING DIMENSION
HEIGHT
mm/in
950 / 37.4 1090 / 42.9
WIDTH mm/in 660 / 26.0 860 / 33.9
DEPTH mm/in 660 / 26.0 860 / 33.9
UNIT WEIGHT kg/lb 70 / 154 93 / 205
PIPE CONNECTION
TYPE BRAZED VALVE BRAZED VALVE
SIZE
LIQUID mm/in 9.5 / 3/8 9.5 / 3/8
GAS mm/in 15.9 / 5/8 19 / 3/4
REFRIGERANT CHARGE kg/lb 2.7 / 5.8 3.5 / 7.7
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB/D17758 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE
CENTRE OF THE UNIT.
07_General data.indd 4007_General data.indd 40 4/28/2009 11:20:48 AM4/28/2009 11:20:48 AM
Vista de pagina 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 129 130

Comentarios a estos manuales

Sin comentarios