Engineering & Physical Data MVCU-2009
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT MCC025C MCC030C
OUTDOOR UNIT MVCU025A MVCU030A
NOMINAL CAPACITY
Btu/h 24000 30900
W 7034 9056
NOMINAL TOTAL INPUT POWER W 2574 3179
NOMINAL RUNNING CURRENT A 13.1 5.5
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
EER W/W 2.73 3.06
REFRIGERANT TYPE R22 R22
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE DUCTED DUCTED
OPERATION SLM WIRED HANDSET SLM WIRED HANDSET
AIR FLOW
SUPER HIGH l/s / CFM - 425 / 900
HIGH l/s / CFM 382 / 810 392 / 830
MEDIUM l/s / CFM 359 / 760 359 / 760
LOW l/s / CFM 288 / 610 335 / 710
EXTERNAL STATIC PRESSURE (SH/H/M/L) Pa / in.wg. - / 41 / 31 / 18 (- / 0.2 / 0.1 / 0.1)
206 / 167 / 127 / 88 (0.8 / 0.7 / 0.5
/ 0.4)
SOUND PRESSURE LEVEL (SH/H/M/L) dBA - / 40 / 39 / 36 49 / 46 / 42 / 38
UNIT DIMENSION
HEIGHT mm/in 261 / 10.3 378 / 14.9
WIDTH mm/in 1200 / 47.2 929 / 36.6
DEPTH mm/in 411 / 16.2 541 / 21.3
PACKING DIMENSION
HEIGHT mm/in 376 / 14.8 415 / 16.3
WIDTH mm/in 1386 / 54.6 1126 / 44.3
DEPTH mm/in 541 / 21.3 631 / 24.8
UNIT WEIGHT kg/lb 25 / 55 39 / 86
CONDENSATE DRAIN SIZE
mm/in
19 / 3/4 19 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 927 / 1965 1251 / 2650
SOUND PRESSURE LEVEL dBA 57 59
UNIT DIMENSION
HEIGHT mm/in 841 / 33.1 841 / 33.1
WIDTH mm/in 572 / 22.5 572 / 22.5
DEPTH mm/in 572 / 22.5 572 / 22.5
PACKING DIMENSION
HEIGHT
mm/in
950 / 37.4 950 / 37.4
WIDTH mm/in 660 / 26.0 660 / 26.0
DEPTH mm/in 660 / 26.0 660 / 26.0
UNIT WEIGHT kg/lb 64 / 141 70 / 154
PIPE CONNECTION
TYPE BRAZED VALVE BRAZED VALVE
SIZE
LIQUID mm/in 9.5 / 3/8 9.5 / 3/8
GAS mm/in 15.9 / 5/8 15.9 / 5/8
REFRIGERANT CHARGE kg/lb 2.0 / 4.4 2.3 / 5.1
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO GB/D17758 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE
CENTRE OF THE UNIT.
07_General data.indd 3907_General data.indd 39 4/28/2009 11:20:48 AM4/28/2009 11:20:48 AM