Operating State and Fault Table
Cooling / Heatpump Model (Universal Board)
Phase Sequencer
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phase
sequencer) is fitted to prevent incorrect wiring of the electrical phases. When the three phases are not connected
correctly, the phase sequencer operates, and the unit will not start. This devise is located in the control box of
the outdoor unit.
The following table shows the LED indicator light for phase sequencer under normal operation and fault conditions.
LED_P
(Red)
LED_R
(Yellow)
LED_S
(Yellow)
LED_T
(Yellow)
Normal Operation On - - -
Reverse Phase Blink Blink Blink Blink
S & T Phase Missing Blink - Blink Blink
T Phase Missing Blink - - Blink
S Phase Missing Blink - Blink -
R Phase Missing - - - -
Overload Blink - - -
Sensor Missing Blink On On On
Notes: 1. “-” means LED off.
2. When R phase missing, no LED or buzzer will indicate the error, but relay 71 (Common) and 81 (NO)
will cut off.
3. The unit will check the discharge sensor availability only during power up.
4. All errors can only recover through manually reset.
Error Code at 7 Segment Display Operation / Faulty Indication
Blink E1 Room sensor contact loose / short
Blink E2 Indoor coil sensor contact loose
Blink E3 Outdoor coil sensor contact loose
Blink E4 Compressor overload / Indoor coil sensor short /
Outdoor coil sensor short
Blink E5 Gas leak
Blink E6 N/A
Blink Heat LED Outdoor defrost (for Heatpump only)