Page 52
The LED indicator on the control panel:
FAN MODE
SLEEP LED Status Analysis
AUTO HIGH MED LOW COOL DRY HEAT FAN
OFF ONLY ONE ON ON OFF OFF OFF OFF -
Normal
Cooling
ON ONLY ONE ON ON OFF OFF OFF OFF - Auto fan cooling
OFF OFF OFF OFF OFF ON OFF OFF OFF - Dry mode
OFF ONLY ONE ON OFF OFF ON OFF OFF - Heating
ON ONLY ONE ON OFF OFF ON OFF OFF - Auto fan heating
OFF ONLY ONE ON OFF OFF OFF ON OFF - Fan
ON ONLY ONE ON OFF OFF OFF ON OFF - Auto fan
OFF ONLY ONE ON ON OFF FLASH OFF OFF - Auto cooling
ON ONLY ONE ON ON OFF FLASH OFF OFF - Auto fan and auto cooling
OFF ONLY ONE ON FLASH OFF ON OFF OFF - Auto heating
ON ONLY ONE ON FLASH OFF ON OFF OFF - Auto fan and auto heating
OFF OFF OFF OFF FLASH OFF OFF OFF OFF -
Fault
Compressor overload
OFF OFF OFF FLASH OFF OFF OFF OFF OFF - Room sensor missing
OFF FLASH OFF OFF OFF OFF OFF OFF OFF -
Outdoor water sensor
missing
OFF OFF FLASH OFF OFF OFF OFF OFF OFF - Indoor coil sensor missing
OFF OFF OFF OFF OFF OFF OFF OFF FLASH - Refrigerant leak
---------FLASH
Water or compressor
problem
By means of pressure readings:
PRESSURE
PROBABLE CAUSE
Data
Circuit
TOO
LOW
TOO
HIGH
High pressure side
Low pressure side
?
?
1. Overcharged with refrigerant;
2.Non-condensable gases in refrigerant circuit;
3. Too warm condenser water;
4. Insuffi cient water fl ow (cooling);
5. Outdoor coil dirty (cooling);
6. Air fi lter clogged/dirty (heating).
High pressure side
Low pressure side
?
?
1.Poor compression/no compression (compressor defective);
2.Reversing valve leak (heating).
High pressure side
Low pressure side
?
?
1. Undercharged with refrigerant;
2. Refrigerant leak;
3. Too low evaporator water;
4. Insuffi cient water fl ow (heating);
5. Outdoor coil dirty (heating);
6. Air fi lter clogged/dirty (cooling).
The most common causes of air conditioner failure to “start” are:
1. Voltage fl uctuation not within ±10% of rated voltage.
2. Power supply interrupted.
3. Control settings improper.
4. Air conditioner is disconnected from main power source.
5. Fuse blown or circuit breaker off.
6. Improper temperature of water loop (water temperature below 13 °C or above 43 °C).