Page 24
Model : MCK 050AR / MWSC 050BR
MCM 050DR / MWSC 050BR
Indoor unit
Terminal block
There must be a three pole
switch with minimum 3 mm
contact gap in the fixed
installation circuit.
Connecting cable
Power supply wire
380-415V/3Ph/50Hz
Outdoor unit
Terminal block
N
T
S
R
E
N
L
COMP
4WV
A
N
L
COMP
4WV
A
F
N
T
S
R
F
2) Electrical parameter
Model
Indoor unit MCK 050AR MCM 050DR
Outdoor unit MWSC 050BR MWSC 050BR
Power source (V/Ph/Hz) 380-415 / 3 / 50
Power input(W)
Cooling 3460 3280
Heating 3580 3560
Running current(A)
Cooling 6.3 5.8
Heating 6.4 6.4
Power supply wire
Section area(mm²) 3.3 4
Quantity 55
Connecting cable
Section area (mm²) 1.5 4
Quantity 66
Comentarios a estos manuales