COMP
WV
4WV
L
N
Indoor terminal
block
Connecting cable
Power supply cable
380-415V/3Ph/50Hz
R
S
T
WV
N
4WV
COMP
N
L
The malfunction wire connecting outdoor unit with indoor unit
The temperature sensor wire connecting outdoor unit with indoor unit
E1
LIVE
E3
E2
A
Outdoor terminal
block
There must be a three pole switch with
minimum 3mm contact gap in the
installation circuit.
F
Model: MCC 050MR / MWSC 050BR
1) Electrical connection
2) Electrical parameter
Model
Indoor unit MCC 050MR
Outdoor unit MWSC 050BR
Power source 380V/3N~/50Hz
Power input
(W)
Cooling 3,460
Heating 3,500
Running current
(A)
Cooling 7.0
Heating 7.3
Power supply wire
Section area(mm²) 2.5
Quantity 5
Connecting cable
Section area (mm²) 1.5
Quantity 6
ó The wiring must be fi rmly connected.
ó Electric wiring must not touch the refrigerant pipe, compressor and moving parts of the fan motor.
ó The wiring between indoor unit and outdoor unit must be fi xed by clamp.
ó All wiring between indoor unit and outdoor unit should be neoprene copper core, and section area of cable
should be in accordance with above requirements.