Page 19
Model: MCC 030MR / MWSC 030BR
The malfunction wire connecting outdoor unit with indoor unit
Connecting cable
The temperature sensor wire connecting outdoor unit with indoor unit
220-240V/1Ph/50Hz
Power supply cable
Indoor terminal
block
Outdoor terminal
block
There must be a double pole switch
with minimum 3mm contact gap in the
installation circuit.
N
COMP
4WV
L
L
N
E1
E2
E3
F
N
4WV
WV
COMP
L
E
N
L
L
N
2) Electrical parameter
Model
Indoor unit MCC 010MR MCC 015MR MCC 020MR MCC025MR MCC 030MR
Outdoor unit MWSC 010BR MWSC 015BR MWSC 020BR MWSC025BR MWSC 030BR
Power source 220V~/50Hz
Power input
(W)
Cooling 740 1,170 1,635 1,950 2,350
Heating 725 1,100 1,470 1,840 2,360
Running current
(A)
Cooling 3.5 5.5 7.6 9.0 10.8
Heating 3.4 5.2 6.8 8.6 10.8
Power supply
wire
Section area(mm²) 2.5 2.5 2.5 2.5 2.5
Quantity 33333
Connecting
cable
Section area (mm²) 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5
Quantity 2222222223
ó The wiring must be fi rmly connected.
ó Electric wiring must not touch the refrigerant pipe, compressor and moving parts of the fan motor.
ó The wiring between indoor unit and outdoor unit must be fi xed by clamp.
ó All wiring between indoor unit and outdoor unit should be neoprene copper core, and section area of cable
should be in accordance with above requirements.
220-240V