IM 985-2 / Page 9 of 38
Water Connections
Allpipingconnectionsshouldbemadeusinggoodplumbing
practices and in accordance with any and all local codes that
may apply.
Note: On left-hand piping units the water supply connection
is on the top. Right hand piping units the water supply
is at the bottom location.
Unit Piping Connection
Eachheatpumpissuppliedwithextendedcoppertubingon
thewater-to-refrigerantcoiland5/8"(16mm)O.D.tubing.
Theconnectionsareforboththesupplyandreturnwater
connections. See Figure 5 for left and right hand connections
locatons.
Shutoff/Balancing Valve Piping
Eachheatpumprequiresashutoffvalveonboththesup-
plyandreturnlinesforeasyserviceabilityandremovalifit
becomesnecessary.
Wesuggestusingourcombinationshutoff/balancingvalves
installedintheeldbetweenthecontractorspipingandthe
heat pump unit. The valve installed on the return line acts as a
balancingvalvetoadjusttheproperwaterow.Anautomatic
owlimitingdeviceisalsoavailableasafactoryinstalled
option.
Eachshutoff/balancingvalvehas1/2"FPTand1/2"FPT
threaded connections.
Attachtheeldinstalledcombinationshut/offbalancing
valvetothebuildingwatersupplyandreturnpiping.
Add the female pipe adapter connection to unit supply and
returncoilconnectionbysweatingtheminplaceusingsilver
solder.
Usingthespeciedhoses,screwthexedendintotheshut-
off/balancingvalve.Removethe1/2"adapterfromtheother
endofthehose.Inserttheadapterintothefemaletting.
Using two crescent wrenches, one to hold the pipe connection
and the second to tighten the adapter, insert the swivel end of
the hose on the adapter and tighten. This completes the hose
connection to standard heat pump equipment.)
Figure 5: Supply and Return Connections Locations for Left- Hand and Right Hand Units (Flat Top and Slope Top)
Right-Hand Piping View
Left-Hand Piping View
IMPORTANT
On left-hand piping units the water sup-
ply connection is on the top. Right-hand
piping units the water supply is at the bot-
tom location.
Table 1: Dimensions (High Sill Units)
Unit Size J K L M P Q R S
007-018
6⅞" 5
1
/
5
" 6¾" 3½" 10¼" 1
3
/
5
" 5¼" 7½"
(175mm) (132mm) (172mm) (90mm) (260mm) (41mm) (134mm) (192mm)