IM 985-2 / Page 31 of 38
Outside Air Damper
Field-installed Option
CAUTION
To prevent inltration of ambient conditions, it is the responsibil-
ity of the contractor to assure that factory installed gasketing
matches up with the wall opening, or that additional material is
used to assure a positive seal.
Cold Weather Operation
Console water source heat pumps may experience erratic
operationduringcoldambientconditionswiththeoutsideair
damper in the open position. See "OperatingLimits"onpage
14, for guidelines.
Multiple Unit Control Panel (MUCP)
for Use With MicroTech® III Unit
Controller
For detailed installation instructions refer to IM 952
The Multiple Unit Control Panel (MUCP) is an accessory
usedwhenupto3-unitsarecontrolledfromasinglethermo-
stat.ConsoleunitsmusthavetheMUCPeld-installedina
remote location, typically close to the units and convenient
for service access.
Amaximumof2boardsmaybeusedtogetherifupto6-units
mustbeconnectedandcontrolledfromasinglethermostat.
Notes: The MUCP control board does not t inside the
console unit control box.
Multi-speed operation is only available with the
optional unit-mounted fan speed switch.
Themultipleunitcontrolboardprovidesthecomponents
necessary to protect the MicroTech III unit controller from
electricaldamagethatmayoccurwhenusingstandardoff-
the-shelfrelays.
ThisversionoftheboardusesVACrelaysandshouldnotbe
usedincombinationwithanyotheraccessoriesorequipment
thatrequireVDCconnectionstothe“G”,“W1”,or“Y1”
terminals (i.e. Boilerless System Kit).