Page 4 of 38 / IM 985-2
Pre-Installation
WARNING
The installer must determine and follow all applicable
codes and regulations. This equipment presents hazards
of electricity, rotating parts, sharp edges, heat and weight.
Failure to read and follow these instructions can result in
property damage, severe personal injury or death. This
equipment must be installed by experienced, trained
personnel only.
1. To prevent damage, do not operate this equipment
for supplementary heating and cooling during the
construction period. Doing so will void the warranty.
2. Inspectthecartonforanyspecictaggingnumbers
indicatedbythefactoryperarequestfromtheinstalling
contractor. At this time the voltage, phase and capacity
shouldbecheckedagainsttheplans.
3. Checktheunitsizeagainsttheplanstoverifythattheunit
isbeinginstalledinthecorrectlocation.
4. Beforeinstallation,checktheavailabledimensionswhere
theunitbeinstalledversusthedimensionsoftheunit.
5. Note the location and routing of water piping, condensate
drain piping, and electrical wiring. The locations of these
itemsareclearlymarkedonsubmittaldrawings.
6. Theinstallingcontractorwillnditbenecialtoconfer
withpiping,sheetmetal,andelectricalforemenbefore
installing any unit.
Note: Check the unit data plate for correct
voltage with the plans before installing the
equipment. Also, make sure all electrical
ground connections are made in accordance
with local code.
7. The contractor shall cover the units to protect the
machinesduringnishingofthebuilding.Thisiscritical
whilesprayingreproongmaterialonbarjoists,
sandblasting,spraypaintingandplastering.Damageto
theunitduetoafailuretoprotectitduringnishingofthe
buildingisnotcoveredbythewarranty.
Receiving and Storage
Uponreceiptoftheequipment,checkcartonforvisible
damage.Makeanotationontheshipper’sdeliveryticket
beforesigning.Ifthereisanyevidenceofroughhandling,
immediatelyopenthecartonstocheckforconcealeddamage.
If any damage is found, notify the carrier within 48 hours to
establishyourclaimandrequesttheirinspectionandareport.
TheWarrantyClaimsDepartmentshouldthenbecontacted.
Do not stand or transport the machines on end. For storing,
eachcartonismarkedwith“up”arrows.
Intheeventthatelevatortransfermakesup-endedposition-
ingunavoidable,donotoperatethemachineuntilithasbeen
in the normal upright position for at least 24 hours.
Temporarystorageatthejobsitemustbeindoor,completely
sheltered from rain, snow, etc. High or low temperatures
naturally associated with weather patterns will not harm
the units. Excessively high temperatures, 140°F (60°C) and
higher, may deteriorate certain plastic materials and cause
permanent damage.
IMPORTANT
This product was carefully packed and thoroughly
inspected before leaving the factory. Responsibility for its
safe delivery was assumed by the carrier upon acceptance
of the shipment. Claims for loss or damage sustained in
transit must therefore be made upon the carrier as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted
on the freight bill or carrier’s receipt, and signed by the
carrier’s agent. Failure to adequately describe such
external evidence of loss or damage may result in the
carrier’s refusal to honor a damage claim. The form
required to le such a claim will be supplied by the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which
does not become apparent until the product has been
unpacked. The contents may be damaged in transit due
to rough handling even though the carton may not show
external damages. When the damage is discovered upon
unpacking, make a written request for inspection by the
carrier’s agent within fteen (15) days of the delivery date
and le a claim with the carrier.
Table 1: Physical Data
Unit Size 007 009 012 015 018
Fan Wheel - D x W (In.)
4.33 x 27.24 4.33 x 27.24 4.33 x 27.24 4.33 x 35.43 4.33 x 35.43
Fan Motor Horsepower
1/30 1/30
1/30 1/18 1/18
Coil Face Area (Sq. Ft.)
1.67 1.67 1.67 2.22 2.22
Coil Rows
2 2 3 2 3
Refrigerant Charge (Oz.) 18.2 19.2 22 29.9 32
Filter, (Qty.) Size (In.)
Low Sill
(1) 23.75 x 8.75
(1) 31.75 x 8.75
High Sill
(1) 29.25 x 9.75 (1) 37.25 x 9.75
Water Connections, Female NPT (In.)
5/8 O.D. 5/8 O.D. 5/8 O.D. 5/8 O.D. 5/8 O.D.
Condensate Connections, Female NPT (In.)
3/4 I.D. 3/4 I.D. 3/4 I.D. 3/4 I.D. 3/4 I.D.
Weight, Operating (Lbs.)
138 144 146 166 171
Weight, Shipping (Lbs.) 158 164 166 196 201