7. Sequential Control For Cool Mode
The starting sequence for indoor fan, outdoor fan and compressors is shown as
below:
2 seconds
Start Indoor fan
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds
outdoor fan 4 compressor 4*
* if available and applicable
The compressors will be turned on one by one depending on the on/off conditions
shown in the above
8. Sequential control for heat mode
The starting sequence for indoor fan, outdoor fan and compressors is as shown
below :
2 seconds 2 seconds
Start Indoor fan all 4 way valves
15 seconds 2 seconds
outdoor fan 1 compressor 1*
15 seconds 2 seconds
outdoor fan 2 compressor 2*
15 seconds 2 seconds
outdoor fan 3 compressor 3*
15 seconds 2 seconds
outdoor fan 4 compressor 4*
15 seconds 15 seconds
Heater 1* Heater 2*
* if available and applicable
The compressors will be turned on one by one depending on the on/off conditions
shown in the above.
B) W1V2 - Chilled Water Fan Coil Unit
Mode Selection
Modes Cool Dry Heat Fan OD
Heatpump, AP XXXXShorted
Cooling, EC X X - X Open
Last Setting Memory Backup
By removing the jumper at JH on the main board.
Wiring Connection
CN4 : To connect to Netware-1 controller (Wired-3 way wire)
CN6 : To connect to LED display (Wireless G6 application)
CN2 : To connect to twin motor board (if required)
T_FULL : To connect to level switch (for Ceiling Cassette only)
T_FULL
CN2
Note :
Only one application either wired or wireless control at one time.