Roof Top Unit : Troubleshooting for optional Global Remote Controller
Before you ask for repair service, check the following points
State of Machine Remote Controller Cause Troubleshooting
(Special Order)
It does not run “ON-OFF” display is not Power failure Press the switch (ON) button after power
light up. No display restoration
appears even when the The power supply is turned OFF Turn the power supply ON
(ON/OFF) button is The fuse in the power supply is gone Replace fuse
pressed The earth leakage breaker is gone Put in the earth leakage breaker.
The wiring phase of power supply is Modify the wiring phase of power supply
mistaken
Air flows out The liquid crystal Improper temperature adjustment After checking the set temperature and inlet
but it does not display shows that it is temperature adjust thermostat (23WA)
cool enough in the state of operation The filter is filled with dust and dirt. Clean up the filter
There are some obstacles at the air Remove the obstacle
inlet and outlet of the units
Windows and doors are open Close the windows and doors
Cool air does not The liquid crystal The restart-preventing circuit is in Wait for a while
come out display shows that operation for 3 minutes (To protect the compressor, a 3-minute restart-
it is in operation preventing circuit is built into the unit.
Therefore, there are occasions sometimes
when the compressor does not start running
immediately. There are cases when it does not
run for as long as 3 minutes.)
Fan runs but compressor does not The set temperature of thermostat is For temperature control, decrease the set
run excessively high for cooling temperature at cooling.
The room temperature is excessively Can not be operated as it is out of temperature
low for cooling control range.
Compressor run but stops Air outlet and inlet are blocked Remove blocking matter
immediately
Water or steam is discharged from At cooling, water which places to It is not a breakdown.
the unit. cooling piping and pipng connection Please use it as it is
part drops
8. Modification to Auto Restart
Auto Restart Feature
Modification on controller board to have unit restart after power failure at default
setting:
Indoor Temp. Set Temp. Fan Speed Mode
Cooling All Temp. 24°C High Cool
model
Heatpump > 20°C 24°C High Cool
model < 20°C 20°C High Heat
I) WM 10/15DR & WM 20/25CR :
a) For challenger C2.2 PCB,
To add a 10k Ohm 5% Carbon, 1/4 W or higher resistor diagonally at S1 On/Off
Switch Board “CHAL2F1”
Front View Reverse View
b) For challenger C2.4 PCB,
To solder a 10k Ohm 5% Carbon, 1/4 W or higher resistor diagonally at S1 On/Off
Switch Board “C2D03F1”
Front View Reverse View