H. WALL MOUNTED INVERTER HEATPUMP UNIT
Model Board
WMV 10FR/SLV10BR VA1.0
LED Indicator Light Display
Cooling / Dry Standby / Fan
(Green / Red) (Red)
Heat Time
(Red) (Green)
Self Diagnosis Table - Indoor LED Display
COOL DRY HEAT STANDBY TIMER
Operation / Faulty Indication
/ Cooling mode
Dry mode
Fan mode
/ Heat mode
/ Auto mode
Defrost operation
Compressor overload protection
Indoor coil sensor contact loose / short
Outdoor coil sensor contact loose / short
Gas leak / compressor overheat
Communication error between indoor
and outdoor
Inverter error / PFC error
Outdoor total current trip / DC peak
31
ON / ON or OFF BLINKING
Outdoor Inverter Display Panel
Error Code Display as LED blinking
Code Error
01 Current transformer error
02 Communication with indoor error
03 Indoor coil sensor error
04 Oudoor coil sensor error
05 Gas leak
06 Coil overload
07 Outdoor air sensor error
08 Compressor discharge sensor error
09 Room sensor error
10 Communication with inverter error
11 PFC error
12 Compressor discharge temperature error
13 Total current overload
14 Inverter DC peak trip (overcurrent)
24 Inverter overvoltage trip
25 Inverter overload trip
26 Inverter overheat trip
27 Inverter CPU error 1
28 Inverter CPU error 2
29 Inverter illegal command in the Master trip
2A Inverter illegal command in the Inverter trip
2C Inverter abnormal in the master trip
2E Inverter external signal trip
Outdoor Board LED
Condition LED
1. Normal Always ON
2. Test run mode Toggle ON/OFF every 1 second
3. Current transformer error Blink once, OFF 3 seconds
4. Inverter trip Blink twice, OFF 3 seconds
(overvoltage, overload, overheat)
5. PFC error Blink 3 times, OFF 3 seconds
6. Total current overload Blink 4 times, OFF 3 seconds
7. Inverter DC peak trip Blink 5 times, OFF 3 seconds