3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Outdoor DB, ˚C
35 37 40
Indoor DB
˚C
Indoor WB
˚C
TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15
5.433 3.787 x y 4.918 3.302
Total capacity, TC
Interpolation Method:
40°C - 35°C 4.918kW - 5.433kW
=> =
40°C - 37°C 4.918kW - x
=> x = 5.227kW
Sensible capacity, SC
Interpolation Method:
40°C - 35°C 3.302kW - 3.787kW
=> =
40°C - 37°C 3.302kW - y
=>y = 3.593kW
38