McQuay M5CK Especificaciones Pagina 121

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 120
IndicaIndica
IndicaIndica
Indica
tor Lights
tor Lightstor Lights
tor Lights
tor Lights
Water Pump
The water pump will on if compressor is on during cooling cycle. The pump will remain on for at least 5 minutes after
the compressor is off.
During mode change from cooling to non-cooling mode, the pump will on for minimum 5 minutes. During defrost cycle,
the pump will on and will on for another 5 minutes once the defrost cycle is terminated.
Water level Switch
This normally close switch is to detect faults in water pump system. It will confirm for 30 seconds for switch open and
60 seconds for switch close.
Once switch is confirmed open, it will force compressor to cut off. If the switch is closed within 5 minutes, the
compressor is allowed to cut in. If the switch does not close for more than 5 minutes, the system will warn user
regarding the fault, the compressor is not allowed to cut in. If the switch is confirmed opened twice within 30 minutes,
the system assumes there are faults.
127
Wired Remote Control (Universal Board)
Cooling / Heatpump Model
Error Code at 7 segment Display Operation/ Faulty Indication
E1 Blinking
Room sensor contact loose/ short
E2 Blinking
Indoor coil sensor contact loose/ short
E3 Blinking
Outdoor coil sensor contact loose/ short
E4 Blinking
Compressor overload
E5 Blinking
Gas leak
E6 Blinking
Pump faulty
Heat LED Blinking Outdoor defrost (for Heatpump only)
Wireless Remote Control (Universal Board)
Cooling : LED Indicator Light Display Heatpump : LED Indicator Light Display
POWER TIMER SLEEP
POWER TIMER HEAT
POWER
TIMER
SLEEP
HEAT
Operation/ Faulty Indication
Timer on
Sleep mode on
Heat mode
Continuously
/
Frost prevention mode
Once every 3 second
Compressor overload
Twice every 3 sec
Pump fault
3 Times every 3 sec
Gas leak
4 Times every 3 sec
Room/ indoor/ outdoor coil sensor contact
Loose/ short
Vista de pagina 120
1 2 ... 116 117 118 119 120 121 122 123 124 125 126 ... 143 144

Comentarios a estos manuales

Sin comentarios