Catalog 1300-1 / Page 32 of 42
Accessories Common to 16" × 42" Units
Dimension 16" x 42" Angled Top 16" x 42" Flat Top
A 11
1
/8" 11
1
/8"
B 24" 24"
C 6
7
/8" 6
7
/8"
Wall Sleeve Extension
PDAC/PDHP Standard 16" × 42" Angled Top Unit
The standard wall sleeve will accommodate the
maximum wall thickness described in Table 2. For
thicker walls, wall sleeve extensions are available
from your local distributor. Air splitters will be
included in the wall sleeve extension as shown in
the illustrations below.
Note:
When installing a new chassis into an existing wall
sleeve with an extension, it will be necessary to relocate
the two air splitters to match the dimensions shown in
the illustrations (see Table 3).
Table 2. Maximum Wall Thickness without Sleeve Extensions
Maximum Wall Thickness
Louver
No Standard
Type
Subbase Subbase
Stamped 3/8" 14
1
/8" 9
1
/2"
Architectural 1
1
/8" 14
7
/8" 10
3
/8"
42
3
/16"
(1072mm)
16
3
/16"
(411mm)
3
3
/4"
(92mm)
44
3
/16"
(1122mm)
18
3
/16"
(1072mm)
Note: Wall Sleeve rough opening when using a Louver
Frame must be 16
5
/8" × 42
5
/8"
Louver Frame
Louver frames should be used for panel wall and
thin wall applications to assure positive anchoring
to the wall. The cabinet/wall sleeve is installed
ush with the outside of the building. The louver
frame is placed around the cabinet/wall sleeve.
Wall Sleeve Extension
42"
Room Side
Air Splitters
as required
16"
16" × 42" Angled Top and Flat Top Unit
B
B
A
C
Table 3. Wall Sleeve Extension Splitter Location Dimensions
Louvers
Two styles of exterior louvers are available.
The standard ush stamped louver is a one-piece
stamped aluminum type that is nished natural and
clear anodized. Attractive, rugged architectural
louvers are extruded aluminum and are nished
natural and clear anodized (optional colors are also
available).
Louvers by others are acceptable as long as they
meet factory specications. They must have a
minimum free area of 70% or a pressure drop not
exceeding .05 in. w.g. at 300 fpm face velocity, and
a blade design that will not cause recirculation of
condenser air.
Flush Stamped Louver