Applied 16" × 42" Chassis Common Features
Digital Touchpad Control
The PDAC/PDHP Standard Touchpad Control is
used to control both an integral air conditioner and
a source of heat. The user will by default control
the electronic controller via the touchpad. The user
can select with a jumper for the unit to receive
commands from a remote thermostat.
Standard (Non-Programmable) Dgital Touchpad
Provides 5-selectable modes of operation:
Sleep, Cool, Cool/Dry, Fan, Heat
Temperature can be displayed in Fahrenheit
(default) or Celsius
Inputs And Outputs
Indoor coil sensor, (ICS)
Outdoor coil sensor, (OCS)
Indoor air sensor, (IAS)
Outdoor air sensor, (OAS)
Remote thermostat, T’STAT (RCBYWG)
Power supply: (24VAC)
Line voltage input, (L1, L2)
Indoor fan standby voltage, (L1STB L2STB)
Control selection: (LUI, T’STAT
Model selection: (AC/E, HP, HP/E)
Time delay bypass, (TEST)
Indoor off fan cycle: (FAN, OFF CYCLE–10,
20, 30, 1 HR)
Outputs
Compressor output, COM
Indoor fan, BLOWER LO, HI
Outdoor fan, OUTDOOR FAN
Electric heater, ELE
Reversing valve, REV VALVE
Keys And Indicators Labels
ON/OFF, FAN SPEED, MODE
7 Push Buttons
FAN MODE, SLEEP
Temp buttons: for
Temp UP and for Temp DOWN
9 LED Indicators
SLEEP, COOL, COOL/DRY, FAN,
HEAT, HIGH, LOW, CYCLE, CONT.
LED 2 Digit Displays No Label
Display Function Legend
Tr = Room Temperature
hI = High Room Temperature
Lo = Low Room Temperature
LA = Low Ambient Lockout
rT = Remote Thermostat Control
tP = Touchpad Control
t = Time
Ts = Temperature Setpoint
Rf = Room Freeze Condition
CF = Coil Freeze Protection
F = Fahrenheit
C = Celsius
LC = Control Lockout Mode
Remote Thermostat Control
The remote thermostat can be any thermostat
that can interface with an electronic thermostat via
RCBWYG terminals. The Control Selection jumper
must be in T’STAT position. During a call the
remote thermostat will pass R back to the controller
on a respective terminal. The push buttons on the
touchpad become inactive in the remote thermo-
stat mode. However, the control pad LED display
will indicate the mode of operation, and the room
temperature.
Note:
In terms of outputs, there are two types of thermostats:
relay contacts and solid state.
If you open the thermostat and don’t see relays then it
must be solid state.
Manufacturers of solid state output thermostats include
loading resistors on their installation kits. They are of 560
Ohm and 3W value. These resistors are meant to load ther-
mostat solid state outputs in order for the output voltage to be
either 0 or 24VAC, i.e. no oating voltage. These resistors are
connected from W, Y, G to common (C), respectively.
You can wire any type of 24Vac thermostat straight into
the REMOTE T’STAT connector of PTAC control boards,
667997101 and 667997201 (Basic and Premium models) and
the control boards will recognize the signals from them.
9- LED
Indicators
LED
2-Digit Display
7- Push Buttons