Vacuuming and charging
Purging the piping and indoor unit
Except for the outdoor unit which is pre-charged with
refrigerant R22, the indoor unit and the refrigerant
connection pipes must be air-purged because the air
containing moisture that remains in the refrigerant
cycle maycause malfunction of the compressor.
• Make sure all pipes are connected securely to
the outdoor and indoor valves.
• Remove the caps from the flare valve and the
service.Take note that there are a total of two
service ports for 5MSX20A/AR, three service
ports for 5MSX25A/AR and four service ports for
5MSX30A/AR.
• Connect the center of the charging gauge to the
vacuum pump.
• Starting from the bottom 3-way valve (labeled A),
connect the charging gauge to the 3-way valve’s
service port. (The numbers of service ports
depend on the O/D unit model).
• Start the vacuum pump. Evacuate for
approximately 30 minutes. The evacuation time
varies with different vacuum pump capacity.
Confirm that the charging gauge needle has
moved towards -760mmHg.
• Proceed to the next 3-way valve and repeat the
steps above.
Caution
• If the gauge needle does not move to -
760mmHg, be ure to check for gas leaks (using
the refrigerant detector) at flare type connection of
the indoor and outdoor unit and repair the leak
before proceeding to the next step.
• Close the valve of the charging gauge and stop
the vacuum pump.
• On the outdoor unit, open the suction valve (3
way) and liquid valve (2 way) (in anti-clockwise
direction) with 4mm key for hexagon sacked
screw.
Additional charge
The refrigerant is pre-charged in the outdoor unit for
specific piping length. Please refer to page 1-5 for
further detail on additional charge.
Service Port
Outdoor Unit 3 ways valve
Flare nut
Refrigerant Piping
Allen key
Suction
valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Vacuum
pump
Open
Close
Close
Close
Hi
Low
Charge operation
This operation must be done by using a gas cylinder
and aprecise weighing machine. The additional
charge is toppedupinto the outdoor unit using the
suction valve via the service port.
• Remove the service port cap.
• Connect the low pressure side of the charging
gauge to the suction service port center of the
cylinder tank and close the high pressure side
of the gauge. Purge the air from the service
hose.
• Start the air conditioner unit.
• Open the gas cylinder and low pressure
charging valve.
• When the required refrigerant quantity is
pumped into the unit, close the low pressure
side and the gas cylinder valve.
• Disconnect the service hose from service port.
Put back the service port cap.
Open
Open
Suction
Valve
Discharge
Valve
Indoor Unit
Outdoor Unit
Liquid side
Gas side
Check
Valve
Close
Hi
Low
R410A must be charged as liquid. Usually R410A cylinder is equipped with a dip-pipe for liquid withdrawal.
If there is nodip-pipe, the cylinder should be inverted so as to withdraw liquid R410A from the valve.
• Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit thoroughly
and then charge the unit with fresh R410A according to the amount recommended in the specification.
!
Caution
21