McQuay M5MAC Guía para resolver problemas Pagina 61

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 66
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 60
60
ii ) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform
satisfactorily, i.e. insufficient cooling. Judgement could be made by measuring temperature
difference of indoor unit’s intake and discharge air as well as running current.
:
Faulty
: Check : Cause : Remedy
Restricted
Insufficient cooling
Air
circulation
Indoor / outdoor coil dirty
(clogged)
Indoor air filter dirty
Clean the coil
Clean the filter
Fan motor malfunction
Obstruction at air inlet /
outlet of indoor / outdoor
unit
Change or repair
the motor
Remove the
obstruction
High cooling
load
Excessive heat source.
e.g. electric kettle
Room overcrowded with
people
Windows / doors wide
open
Remove or reduce
heat source
Reduce number
of people in the room
Close the
windows / doors
Refrigerant
circuit
Restriction e.g. at
strainer, capillary, filter
dryer, etc.
Refrigerant short charge
or refrigerant leakage
Add refrigerant.
Repair leakage
if detected
Repair clogging
or replace faulty
components
Compressor
Less or no compression
(Low running current)
Replace compressor
Satisfactory operation with temperature difference of air
intake & discharge of indoor unit 8°C to 13°C. *
( * value is for reference only )
Vista de pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66

Comentarios a estos manuales

Sin comentarios