MCM-2009Ceiling ExposedSplit SystemsCatalog MCM 020D/DR MCM 025D/DR MCM 030D/DR MCM / M5CM 040D/DR MCM / M5CM 050D/DR MCM / M5CM 062C/CRModels:
Application InformationOperating RangeEnsure the operating temperature is in allowable range.Cooling only!Caution :The use of your air conditioner out
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.98Electric
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.99Electric
Electrical Data - Cooling only (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.101Electri
Wiring Diagrams102Cooling onlyIndoor UnitModel : MCM 020 / 025DOutdoor UnitModel : MLC 018 / 020 / 025C
Indoor UnitModel : MCM 030D103Outdoor UnitModel : MLC 028C
104Indoor UnitModel : MCM 030DIndoor UnitModel : MLC 030C
105Indoor UnitModel : MCM 040DOutdoor UnitModel : MLC 035 / 040C (1 Phase)
106Indoor UnitModel : MCM / M5CM 040D, MCM 050CDOutdoor UnitModel : MLC / M5LC 040C, M5LC 035C , MLC 050C (3 Phase)
107Indoor UnitModel : M5CM 040DOutdoor UnitModel : M5LC 035C (1 Phase)
Refrigerant Circuit DiagramModel: MCM 020D – MLC 018 / 020C MODEL: MCM 025D – MLC 025C9
Indoor UnitModel : M5CM 040D108Outdoor UnitModel : M5LC 040C (1 Phase)
Indoor UnitModel : M5CM 050COutdoor UnitModel : M5LC 050C109
110Indoor UnitModel : MCM / M5CM 062COutdoor UnitModel : MLC / M5LC 061C
111Indoor UnitModel : MCM 020 / 025DROutdoor UnitModel : MLC 018 / 020 / 025CR Heatpump
Indoor UnitModel : MCM 030DROutdoor UnitModel : MLC 028CR112
113Indoor UnitModel : MCM 030 / 040DROutdoor UnitModel : MLC 030 / 035/ 040CR (1 Phase)
114Indoor UnitModel : MCM 030 / 040/ 050DROutdoor UnitModel : MLC 030/ 040/ 050CR (3 Phase)
Indoor UnitModel : MCM / M5CM 040DROutdoor UnitModel : M5LC 035CR (1 Phase)115
Indoor UnitModel : M5CM 040DR116Outdoor UnitModel : M5LC 040CR (1 Phase)
Indoor UnitModel : M5CM 040DROutdoor UnitModel : M5LC 035 / 040CR (3 Phase)117
Model : MCM 030D – MLC 028CModel : MCM 030D – MLC 030CMCM 040D – MLC 035 / 040CMCM 050D – MLC 050CMCM 062C – MLC 061C10
Indoor UnitModel : M5CM 050DR118Outdoor UnitModel : M5LC 050CR
119Indoor UnitModel : MCM 062CROutdoor UnitModel : MLC 061CR
Indoor UnitModel : M5CM 062CROutdoor UnitModel : M5LC 061CR120
Outdoor UnitModel : MLC 030C (Cooling only)50Hz / 1 Phase / 220 ~ 240V121High Ambient UnitOutdoor UnitModel : MLC 040 / 050C (Cooling only)50Hz / 3
122High Ambient UnitOutdoor UnitModel : MLC 030CR (Heatpump)50Hz / 1 Phase / 220 ~ 240VOutdoor UnitModel : MLC 040 / 050CR (Heatpump)50Hz / 3 Phase /
Servicing and MaintenanceWarning: Disconnect from main supply before servicing the air conditioner.The unit is designed to give long life operation
The design of the MLC outdoor series allows servicing to be carried out readily and easily. The removal of the topside, front and back panel make almo
TTTTTrrrrroubouboubouboubleshootingleshootingleshootingleshootingleshooting125When a malfunction of the air conditioner unit is detected, immediately
Diagnostic GuidelinesBy means of pressure readings:Data Pressure Circuit Too low A little low Normal A little high Too high Probable cause High si
By Means Of Diagnostic Flow Chart :Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/heating. “Starting failu
11Model : M5CM 040D – M5LC 035 / 040CM5CM 050D – M5LC 050CM5CM 062C – M5LC 061CModel : MCM 020DR – MLC 018 / 020CR
128ii ) Diagnosis of Refrigerant Circuit / ApplicationThere might be some causes where the unit starts running but does not perform satisfactorily, i.
129Satisfactory operation with temperature difference of air intake & discharge of indoor unit14°C to 20°C. *( * value is for reference only )Rest
Exploded View and Parts ListModel : MCM 020 / 025 D/DR130No Description Part No. No Description Part No.1 Top Panel R01014022475 17 Side Frame Assy.,
Model : MCM 030 D/DR131No Description Part No. No Description Part No.1 Bracket Hanger, Left R01014032844 16 Drain Hose Assy. R501240251132 Control Bo
Model : MCM / M5CM 040 / 050 D/DR132No Description Part No. No Description Part No.1 Bracket Hanger, Left R01014032844 17 Air Intake Grille Frame Hold
Model : MCM / M5CM 062 C/CR133No Description Part No. No Description Part No.1 Top Back Panel R50015039175 15 Terminal Box R010140219612 Coil Holder
134Model : MLC 018 / 020CNo Description Part No No Description Part No1 Assy. Base Pan R50014078281 13 Terminal Cover Panel R010140708382 Assy. Outdoo
135Model : MLC 025 / 028CNo Description Part No No Description Part No1 Assy. Base Pan R50014073884 13 Terminal Cover Panel A010140708382 Assy. Outdoo
Model : MLC 020CR136No Description Part No No Description Part No1 Assy. Base Pan R50014078281 13 Terminal Cover Panel R010140708382 Assy. Outdoor Coi
Model : MLC 025 / 028CR137No Description Part No No Description Part No1 Assy. Base Pan R50014073884 14 Assy. Control Panel2 Assy. Outdoor Coil MLC 02
12Model : MCM 025DR - MLC 025CRMCM 030DR - MLC 028CR Model : MCM 030DR - MLC 030CRMCM 040DR - MLC 040CRMCM 050DR - MLC 050CR
Model: MLC 030 / 040C/CRNo Description Part No No Description Part No1 Assy. Base Pan R50014053238 11 Bracket, Fan Motor R010140532322 Assy. Flare Val
139Model: M5LC 035/040C/CR1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENo Description Part No No Description Pa
140Model : MLC 050 / 061CRNo Description Part No No Description Part No1 Assy. Base Pan R50014053238 11 Bracket, Fan Motor2 MLC 050C/CR MLC 050C/CR R0
141Model : M5LC 050/061C/CR1) ALL SPECIFICATIONS ARE SUBJECT TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICENo Description Part No No Description P
291© 2009 McQuay International +1 (800) 432-1342 www .mcquay. com Products manufactured in an ISO certified facility. This document contains the mo
13Model : M5CM 040DR – M5LC 035 / 040CRM5CM 050DR – M5LC 050CRM5CM 062CR – M5LC 061CRModel : MCM 062CR – MLC / M4LC 061CR
G7 Remote Controller14
COOLDRYHEATMEDHIGHAUTOMODETEMPSENSORON/OFFSLEEPLOWTIMER82593641FANFAN ON/OFFTEMPSLEEPTIMER MODE7123456107SWINGSWINGFANSLM AC-5300 (OPTIONAL)1. “ON/OFF
Operating State and Fault TableWireless Remote Controller - HandsetCooling: LED Indicator Light Display Heatpump : LED Indicator Light Displ
Phsae SequencerThe unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device (phasesequencer) is fitted to pr
Nomenclature ... 1 - Product Line UpFeatures
InstallationSharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.(1) Installation of Outdoor UnitPreliminary Site S
Please ensure that the following steps are taken :• Check the gradient for drainage flow as recommended in Figure B.• Provide clearance for easy servi
MCM 062C • Provide the installation space as shown in Figure D. MCM-D MCM 062CFigure CFigure D20
Installation - Ceiling Exposed TypeSTEP 1Remove air intake grille, side panel, side close-up and hanger bracket from the unit; see Fig E.Figure ESTEP
Installation - Floor Standing TypeSTEP 1Remove air intake grille, side panel, side close-up and side panel from the unit; see Fig E.STEP 2Position th
23(2) Installation of Outdoor UnitAs condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maxim
(3) Refrigerant PipingMaximum Pipe Length and Maximum Number of Bends• When the pipe length becomes too long, both the capacity and reliability drop.
4) WiringELECTRICAL CONNECTIONS• Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICALCODES for f
Diagram shows typical charging method.26Note : R407C - Fix filter dryer R22 - Nil R410A - Nil(6) Additional Charge• The refrigerant
Special Precautions When Dealing with Refrigerant R410A Unit1) What is New Refrigerant R410A?R410A is a new HFC refrigerant which does not damage the
Nomenclature C A F A - Model Type R : Heatpump Omitted if Cooling Only Series C : C Series D : D Series Capacity 040 : 40,000 Btu/h Model Name CM
d) When charging R410A, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R4
(6) Overall Checking• Ensure the following, in particular:1. The unit is mounted solidly and rigid in position.2. Piping and connections are leak proo
Sound Data30Overall Noise125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz A(dBA) CriteriaHigh 45 46 47 46 41 38 29 50 45Medium 42 43 45 42 38 34 24 47 41Low 36 3
31MCM 020D/DR NC CURVESMCM 025D/DR NC CURVES
32MCM30D/DR NC CURVESMCM / M5CM 040D/DR NC CURVES
33MCM / M5CM 050D/DR NC CURVESMCM / M5CM 062C/CR NC CURVES
Engineering and Physical DataGeneral Data - Cooling only (R22)341) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
351) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
361) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
371) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
Outdoor2 O A P C A - Model Type R : Heatpump Omitted if Cooling Only Series C : C series Capacity 020 : 20,000 Btu/h Model Name LC : Single Split Co
381) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
39General Data - Heat Pump (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED A
401) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
411) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
421) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
431) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.3) NOMIN
44General Data - Cooling Only (R410A)M5LC 035C M5LC 040CBtu/h 33000 / <33300> 38500 / <38500>W 9670 / <9670> 11280 / <11280>W
45General Data - Cooling Only (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TES
461) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151
471) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
Outdoor3 G E F A - Model Type R : Heatpump Omitted if Cooling Only Series B : B Series C : C Series Capacity 030 : 30,000 Btu/h Model Name LC : Sin
Components Data (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.48MLC 018C MLC 020Cmm/inmm/inmm/incm3 / fl
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.49Components Data (R22)mm/inmm/inmm/incm3 / fl.oz.mm/inmm/inmm/
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.50Components Data (R22)MLC 028C MLC 030Cmm/inmm/inmm/in457 / 18
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.51Components Data (R22)MLC 035C MLC 040Cmm/inmm/inmm/inMINERAL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.52Components Data (R22)MCM 050D MCM 062CMLC 050C MLC 061CABS AL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.53Components Data (R22)MLC 018CR MLC 020CRmm/inmm/inmm/incm3 /
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.54Components Data (R22)mm/inmm/inmm/incm3 / fl.oz.mm/inmm/inmm/
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.55Components Data (R22)MLC 028CR MLC 030CRmm/inmm/inmm/in457 /
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.56Components Data (R22)MLC 035CR MLC 040CRmm/inmm/inmm/inMINERA
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.57Components Data (R22)MCM 050DR MCM 062CRMLC 050CR MLC 061CRAB
Product Line UpIndoor UnitMCM-D Series Product Line Up (R22)Indoor UnitM5CM-D Series Product Line Up (R410A)4ControlL208A PCBSLMG7 HandsetCE MarkW/out
Component Data (R410A)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.58M5LC 035C M5LC 040Cmm/inmm/inmm/inSCROL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.59Component Data (R410A)M5CM 050D M5CM 062CM5LC 050C M5LC 061C4
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.60Component Data (R22)MLC 035CR MLC 040CRmm/inmm/inmm/inSCROLL
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.61Component Data (R410A)M5CM 050DR M5CM 062CRM5LC 050CR M5LC 06
62Safety Devices1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.MLC 018C MLC 020CN/A N/AOPEN kPa / psiN/A N/ACL
631) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesMCM 050D MCM 062CMLC 050C MLC 061CNC NCOPEN kPa
641) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesMLC 035CR MLC 040CRNC NCOPEN kPa / psi2937 / 42
651) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.Safety DevicesM5LC 035C M5LC 040CNC NCOPEN kPa / psi2937 / 42
Performance DataInterpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC atthose temperatures which
67Details:1st Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 24°C DB, 15°C WBOutdoor Condition: 35°C DBTotal capaci
Outdoor UnitMLC-C Series Product Line Up5ellirGebuT .paCVXTniF dloGtiK tneibmA hgiHtiK tneibmA woLrotcatnoChctiwS erusserP hgiHhctiwS erusserP woLWS .
682nd Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 35°C DBTotal capacity,
693rd Step:To obtain the Total capacity and Sensible capacity for(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DBTotal capacity,
R22 Models(Cooling only)Model : MCM 020D / MLC 018CModel : MCM 020D / MLC 020B70TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
R22 Models(Cooling only)Model : MCM 025D / MLC 025CModel : MCM 030D / MLC 028C71TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
72R22 Models(Cooling only)Model : MCM 030D / MLC 030CModel : MCM 040D / MLC 035CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
73R22 Models(Cooling only)Model : MCM 040D / MLC 040CModel : MCM 050D / MLC 050CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)
R22 Models(Cooling only)Model : MCM 062C / MLC 061C74TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)1517.094 10.28
R22 Models(Heatpump)Model : MCM 020DR / MLC 018CRCooling ModeHeating Mode75TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k
76R22 Models(Heatpump)Model : MCM 020DR / MLC 020CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
77R22 Models(Heatpump)Model : MCM 025DR / MLC 025CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k
Outdoor UnitM5LC-C Series Product Line Up6GrilleCap. TubeTXVGold FinHigh Ambient KitLow Ambient KitContactorHigh Pressure SwitchLow Pressure SwitchNan
78R22 Models(Heatpump)Model : MCM 030DR / MLC 028CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(k
79R22 Models(Heatpump)Model : MCM 030DR / MLC 030CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
80R22 Models(Heatpump)Model : MCM 040DR / MLC 035CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
81R22 Models(Heatpump)Model : MCM 040DR / MLC 040CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
82R22 Models(Heatpump)Model : MCM 050DR / MLC 050CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
83R22 Models(Heatpump)Model : MCM 062CR / MLC 061CRCooling Mode Heating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(
84R410A Models(Cooling only)Model : M5CM 040D / M5LC 035CModel : M5CM 040D / M5LC 040CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) S
85R410A Models(Cooling only)Model : M5CM 050D / M5LC 050CModel : M5CM 062C / M5LC 061CTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) S
86R410A Models(Heatpump)Model : M5CM 040DR / M5LC 035CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
87R410A Models(Heatpump)Model : M5CM 040DR / M5LC 040CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
FeaturesUltra Slim New Stylish Design ProfileThis unit is contemporary in design and match even the most up to date interior decor. The slim, roundpro
88R410A Models(Heatpump)Model : M5CM 050DR / M5LC 050CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
89R410A Models(Heatpump)Model : M5CM 062CR / M5LC 061CRCooling ModeHeating ModeTC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) T
Dimensional DataIndoor UnitModel : MCM - D SERIES (Cooling only and Heatpump)All dimension in mm90MODEL MCM 020D/DR MCM 025D/DR MCM 030D/DR MCM
Model : MCM 062C/CR91All Dimension in mmMCM A(GRILL) B C D E F G H I J K L O T X 062C 1750 40 36 1930 1830 680 352 292 285 140 1880 250 126 13
Outdoor UnitModel : MLC 018C/CR MLC 020 / 025 / 028C/CRNote : Dimension in mm92FOR 25 / 28C/CR ONLYMODEL A B C
Model : MLC 030 / 035 / 040 / 050C/CR M5LC 035 / 040 / 050C/CR931030.0746.5141.550.085.040.040.0320.0400.0488.0448.0850.025.0Model : MLC / M5LC
Electrical DataElectrical Data - Cooling Only (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.95Electric
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.96Electric
Electrical Data - Heat Pump (R22)1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.2) ALL UNITS ARE BEING TESTED