McQuay M5MAC Guía para resolver problemas Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 66
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
30
Model Diff. Temperature
1 compressor Not. Applicable
2 compressors 0.5°C
3 compressors 1.0°C
4 compressors 1.5°C
Dip switch 6
a. Fan off Off
b. Fan on On
Model Auto Cool Heat Fan
SQCn - X - X
SQHnh - X X X (Dip switch 5 = off)
SQHnh X X X X (Dip switch 5 = on)
JH1 Setting
a. Last memory backup JH1 Plugged
b. Without last memory backup JH1 Removed
The default differential temperature is base on number of compressor model, the setting is as
below:
4. Hot Keep Option
5. Operating Modes
The system has 4 operating modes to select with respect to each model selection:
Where x denotes modes available
n = number of compressor(s)
h = number of heater(s)
6. Last Memory Functions
ThepowerupsettingsforeitherwithorwithoutthelastmemorybackupisbasedontheJH1
setting.