Unit Hanging
Confirm the pitch of the hanging rod is 790.0mm X 620.5mm (M5CKX-A)
Hold the unit and hand it on the hanging rod with the nut and washer.
Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bol to prevent
unit falling and vibration.
Open the ceiling board along the outer edge of the paper installation template.
Drain Piping Work
Note: This indoor unit use drain pump for condensed water drainage. Install the unit
horizontally to prevent water leakage or condensation around the air outlet.
Drain Test
Ceiling
Board
35.0mm (MCK-A/B)
30.0mm (MCK-C)
Drain pipe must be downward gradient for smooth drainage.
Avoid the drain pipe from up and down slope to prevent reversal
flow.
During the drain piping connection, be careful not to exert extra
force on the drain connector at indoor unit.
The outside diameter of the drain connection at the flexible drain
hose is 20mm.
Be sure to provide heat insulation (polyethylene foam with
thickness more than 8.0mm) on the drain piping to avoid the
condensed water dripping inside the room.
Connect the main drain pipe to the flexible drain hose.
Feed water from flexible drain hose and check the piping for
leakage.
When the test is completed, connect the flexible drain hose to
the drain connector on the indoor unit.