DYNAMIC SELF BALANCING
CONTROL VALVE
FlowCon SM with BACnet actuator
- 3 -
Choose whether or not to enable flush at
startup in BV.53 (programming menu step 4).
Flush enabled results in the actuator open-
ing the valve almost fully if no control sig-
nal is registered at start-up.
This function is only available if control signal
type is V or mA.
Options:
0 = disable
1 = enable
Choose whether or not to enable password
protection of the actuator in BV.54 (program-
ming menu step 11).
If password protection is enabled, the actua-
tor requires a password to enter the program-
ming menu via the buttons on the actuator.
Options:
0 = disable
1 = enable
If the actuator is of the type SM.0.0.0.6
(failsafe and BACnet), please choose the
direction of the failsafe action in BV.18
(programming menu step 12).
Options:
0 = open
1 = close
Please note, that the settings and values can-
not be altered through BACnet while the alarm
menu or the programming menu is entered
on the actuator.
Condition of the
actuator through BACnet.
Besides checking the values of the objects
already described, the following information
is available through BACnet:
Check the current flow rate (not measured)
in AV.68. If AV.68=0, the flow rate is less
than the minimum defined flow rate (for in-
formation about minimum defined flow rate
please see the tech note, which is always
available at www
.flowcon. com).
T
o know whether the valve is fully closed,
please check the motor position in AV.98, if
AV.98=0% the valve is fully closed.
Check the appropriate pressure range in
MSV.44. Values:
1 = NA
2 = 32-320kPaD
3 = 40-320kPaD
4/5/7/10 = 35-400kPaD
6 = 80-400kPaD
8/9/11 = 60-400kPaD
Check the actuator state in MSV.45.
Values:
1 = normal operation
2 = calibration mode
3 = flush mode
4 = auto-stroke
5 = alarm (at least one alarm has been
activated)
6 = failsafe (failsafe action has begun)
If MSV.45=5, please check for any alarms in
BV.55 - BV.62.
Values:
0 = no alarm
1 = alarm activated
If MSV.40=1 or MSV.40=2, check the con-
trol signal value in AV.141. If MSV.40=3,
check the control signal in MSV.42.
Check unit and value of the feedback sig-
nal in AV.164.
If the actuator is of the type SM.0.0.0.6
(failsafe and BACnet), check the battery
capacity (0-100%) in AV.140.