DYNAMIC SELF BALANCING
CONTROL VALVE
FlowCon SM with BACnet actuator
- 2 -
Programming
of the actuator through BACnet.
Please note that change of settings through
BACnet is not available while one of the
menus is entered on the actuator itself.
In this instruction:
AV = Analog Value
BV = Binary Value
MSV = Multi-State Value.
Default values are underlined.
Choose which valve the actuator is mounted
on in MSV.38 (programming menu step 2).
Options:
1 = SM.0.0 (no valve)
2 = SM.1.1
3 = SM.2.1
4 = SM.3.0
5 = SM.3.1
6 = SM.3.2
7 = SM.4.1
8 = SM.4.2
9 = SM.4.3
10 = SM.5.1
11 = SM.5.2
Choose relevant unit in MSV.39
(programming menu step 3).
Options:
1 = l/sec
2 = GPM
3 = l/hr
Choose operational direction in BV.17
(programming menu step 10).
Options:
0 = NO (normally open)
1 = NC (normally closed)
Choose maximum flow rate in AV.62
(programming menu step 9).
The input will automatically be rounded off to
the nearest available maximum flow rate for
the chosen valve. Please see the relevant
tech note for information about the maximum
flow rates available for each valve.
Choose control signal type in MSV.40
(programming menu step 5).
Options:
1 = V
2 = mA
3 = digital (2-position / 3-point-floating)
4 = BACnet
If MSV.40=1 (V) or MSV.40=2 (mA), please
check control signal range. Choose minimum
value for the control signal in AV.138 (pro-
gramming menu step 6) and maximum value
for the control signal in AV.139 (programming
menu step 7). The range must be at least
3.0V respectively 6.0mA and maximum ran-
ges are 0-10V respectively 0-20mA.
If MSV.40=4 (BACnet), please choose BAC-
net fallback timeout in AV.143 (options: 1-60
minutes, defalult:10) and BACnet fallback
action (options: 1=close, 2=stop, 3=open,
4=midway) in MSV.43 to define the action to
be taken if the actuator does not get a value
for the control signal within the timeout period
since the last time it received a control sig-
nal. Administrating the control signal through
BACnet is done by writing the present-value
of AV.141 in the range of 0.0-100.0%.
Choose feedback signal type and range in
MSV.41 (programming menu step 8).
Options:
1 = 2-10V
2 = 0-10V
3 = 4-20mA
4 = auto
Option 4 is only available and default if control
signal type is V or mA (this option sets feed-
back signal type and range to the same as
control signal type and range). If control signal
type is digital or BACnet, option 1 is default.