1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
General Data - Heat pump
M5CMX020ER M5CMX025ER
M5LCX020CR M5LCX025CR
Btu/h
18000 21000
W
5275 6155
Btu/h
19000 22000
W
5568 6448
W
1663 2025
W
1662 2047
A
7.30 8.89
A
7.30 9.02
V/Ph/Hz
220 - 240 / 1 / 50 220 - 240 / 1 / 50
W/W
3.15 3.04
W/W
3.33 3.15
R410A R410A
OUTDOOR EXV OUTDOOR EXV
AUTOMATIC LOUVER (UP & DOWN) AUTOMATIC LOUVER (UP & DOWN)
WIRELESS OR WIRED
MICROCOMPUTER REMOTE
CONTROL
WIRELESS OR WIRED
MICROCOMPUTER REMOTE
CONTROL
l/s / CFM
245 / 520 274 /
580
l/s / CFM
217 / 460 250 / 530
l/s / CFM
192 / 406 231 / 490
dBA
48 / 46 / 43 50 / 47 / 46
mm/in
218 / 8.6 218 / 8.6
mm/in
1080 / 42.5 1080 / 42.5
mm/in
630 / 24.8 630 / 24.8
mm/in
297 / 11.69 297 / 11.69
mm/in
1197 / 47.13 1197 / 47.13
mm/in
740 / 29.13 740 / 29.13
kg/lb
27 / 59.5 27 / 59.5
mm/in
19.05 / 3/4 19.05 / 3/4
l/s / CFM
615 / 1300 755 / 1600
dBA
53 56
mm/in
757 / 29.8 757 / 29.8
mm/in
855 / 33.7 855 / 33.7
mm/in
328 / 12.9 328 /
12.9
mm/in
785 / 30.9 785 / 30.9
mm/in
983 / 38.7 983 / 38.7
mm/in
405 / 15.9 405 / 15.9
kg/lb
50 / 110.3 50 / 110.3
FLARE VALVE FLARE VALVE
LIQUID mm/in
6.4 / 1/4 6.4 / 1/4
GAS mm/in
12.7 / 1/2 15.8 / 5/8
kg/lb
1.30 / 2.86 1.40 / 3.08
MEDIUM
INDOOR UNIT
CONTROL
AIR DISCHARGE
OPERATION
PACKING DIMENSION
HEIGHT
UNIT WEIGHT
CONDENSATE DRAIN SIZE
WIDTH
OUTDOOR UNIT
HIGH
MODEL
INDOOR UNIT
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (CO
OLING)
NOMINAL TOTAL INPUT POWER (HEATING)
EER
REFRIGERANT TYPE
REFRIGERANT CONTROL (EXPANSION DEVICE)
COP
POWER SOURCE
NOMINAL COOLING CAPACITY
DEPTH
AIR FLOW
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
WIDTH
SOUND PRESSURE LEVEL (H/M/L)
LOW
UNIT DIMENSION
HEIGHT
REFRIGERANT CHARGE
AIR FLOW
DEPTH
PACKING DIMENSION
HEIGHT
DEPTH
OUTDOOR UNIT
TYPE
SIZE
SOUND PRESSURE LEVEL
WIDTH
UNIT DIMENSION
UNIT WEI
GHT
PIPE CONNECTION
WIDTH
DEPTH
HEIGHT