M5LCX-2009
Indoor Unit
Ceiling
Board
Unit Hanging
Drain Piping Work
Note: This indoor unit use drain pump for condensed water drainage. Install the unit horizontally to
prevent water leakage or condensation around the air outlet.
Drain Test
35.0mm (MCK-A)
30.0mm (MCK-C)
M5CKX-A/C
Drain pipe must be downward gradient for smooth
drainage.
Avoid the drain pipe from up and down slope to prevent
reversal flow.
During the drain pipe connection, be careful not to exert
extra force on the drain connector at the indoor unit.
The outside diameter of the drain connection at the
flexible drain hose is 20mm.
Be sure to provide heat insulation (polyethylene foam
with thickness more than 8.0mm) on the drain piping to
avoid the condensed water dripping inside the room.
Connect the main drain pipe to the flexible drain hose.
Feed water from flexible drain hose and check the piping
for leakage.
When the test is completed, connect the flexible drain hose
to the drain connector on the indoor unit.
MAIN DRAIN PIPE
FEED WATER
FLEXIBLE
DRAIN HOSE
INDOOR UNIT
Pipe clamp
Good
Bad
Confirm the pitch of the hanging rod is 790.0mm X 620.5mm (M5CKX-A)
Hold the unit and hand it on the hanging rod with the nut and washer.
Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bol to prevent unit falling
and vibration.
Open the ceiling board along the outer edge of the paper installation template.