Compressor Stopped Troubleshooting Instructions
Keep the Main Power Supply ON
Open up the Outdoor Unit’s Top Panel or Service Panel
Notice the Yellow LED on the P.C.Board
DO NOT TOUCH ANY OF THE
WIRES INSIDE THE UNIT!
Count the number of blinks
indicated by the LED
Blink Fault Indication Corrective Action
1 OutdoorAmbient Sensor Error Check ambient sensor wire and connection
2 Outdoor Coil Sensor Error Check coil sensor wire and connection
3
Outdoor Discharge Sensor Error /
Compressor Overheat Indication
Check discharge sensor wire and connection / Not
enough refrigerant / Indoor overload / Outdoor fan not
functioning
4 DC Compressor Feedback Call local dealer
5 Communication Error Check Interconnection communication wire
relaed lacol llaC tnerruC revO 6
noitcennoc dna eriw rosserpmoc kcehC daoL oN 7
8 Over / UnderVoltage Check power supply
9 DC Compressor Start Failure Call local dealer
10 Cooling Overload Check whether outdoor unit is blocked or not
tratser neht revo si tsorfed llit tiaW tsorfeD 11
12 IPM Protection Check IPM
13 EEPROM Read Error Change EEPROM
14 EEPROM Write Error Change EEPROM
17 Outdoor Suction Sensor Error Check suction sensor wire and connection
*If the problem persist, contact your local dealer straight away
(Applicable to Inverter System Only)