There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insufcient
cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and dis-
charge air as well as running current.
Hi gh cooling
load
Remo ve or red uc e heat source
Red uc e num ber of pe ople in the roo m
Cl ose the w in dow s / doo rs
Refrigerant
circuit
Refrigerant sho rt c har ge
or re frigerant leakage
Ad d refri gera nt. Repa ir l e akage if de tected
Repa ir clo gg in g or replace fa ult y com po nents
Com press or
Less or no comp re ssi on
(Low running curren t)
Rep lace c omp ress or
Satisfactor y op era tion with temp eratur e differenc e of air
intake & disch arge of indoor un it 8°C to 13°C . *
( * value is for refe renc e on ly )
: Faulty
: Check : Cause : Remedy
Room over crowded with
people
Windows/doors wide open
Restriction e.g. atstrainer,
capillary, filter dryer, etc.
Obstruction
at air inlet / outlet of indoor /
outdoor unit
Excessive heat source.
e.g. electric kettle
Fan motor malfunction
Indoor air filter dirty
Indoor/outdoor coil dirty
(clogged)
Remove the obstruction
Clean the filter
Air
circulation
Insufficient cooling