M5HDC-2010
Troubleshooting
Diagnostic Guidelines
No Cooling / Heating
Unit fail to start
Check power supply
- voltage
- phase
- frequency
Check settings of remote control box
Compressor fails to start
Check circuit breake & fuse
Check power source cord
Fan fails to start
Fan Motor Capacitor defective
Loose Connections,
Contactors
Irregular motor resistance (
)
& insulation (M
)
Replace Fan Motor
Compressor Motor damaged ( to replace compressor)
Thermostat setting too high
Protection Device Actuated
Reset
Compressor locked (to replace compressor)
Voltage supply not within range
Check motor resistance (
) and insulation (M
)
Compressor
Capacitor Defective
Loose Connections,
Improper wiring
Regular but fails
to start
Irregular
By means of pressure reading:
Pressure
Data
Circuit
Too low
A little low
Normal
A little high
Too high
Probable cause
High side
Low side
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
High side
Low side
High side
Low side
High side
Low side
1. Air intake temperature of indoor unit too high.
1. Poor compression / no compression
(compressor defective)
2. Reversing valve leaking.
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked / seized (heating).
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
By Means Of Diagnosis Flow Chart
Generally, there are two kinds of troubles, i.e. starting failure and insufficient cooling / heating.
“Starting Failure” iscaused by electrical defect while “Insufficient Cooling / Heating” is caused
by improper application or defects inrefrigerant circuit.