Performance Data
Performance Data
1
st
Step
Extrapolation of Indoor WB
Find TC, SC for
(a) Indoor: 24°C DB, 15°C WB
Outdoor: 35°C DB
(b) Indoor: 24°C DB, 15°C WB
Outdoor: 40°C DB
2
nd
Step
Interpolation of Indoor DB
Find TC, SC for
(a) Indoor: 23°C DB, 15°C WB
Outdoor: 35°C DB
(b) Indoor: 23°C DB, 15°C WB
Outdoor: 40°C DB
3
rd
Step
Interpolation of Outdoor DB
Find TC, SC for
(a) Indoor: 23°C DB, 15°C WB
Outdoor: 37°C DB
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible
capacity, SC at those temperatures which are not stated out in the table.
Example:
Model: M5CC020CR - M5HDC020AR
Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Solution:
Overall
Based on the Performance Table
1. Refer to the Indoor DB column,
- 23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C
WB and 17°C WB during 24°C indoor DB is required)
3. Refer to the Outdoor DB column,
- 37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.