Installation and Maintenance Manual IM 980-1ThinLine 3G Vertical Fan CoilsType FCVC, FCVH, FCVS and FCWC Vertical DesignGroup: Applied Air SystemsPar
10 Daikin IM 980-1Installation1 Vent the vacuum breaker line to atmosphere or connect it into the return main at the discharge side of the steam trap.
Daikin IM 980-1 11InstallationInstall a strain relief and pass the wires through the strain relief into the junction box. Make the connections and rei
12Daikin IM 980-1Installation3 Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents.4 Start
Daikin IM 980-1 13Operation and MaintenanceOperation and MaintenanceControlsA wide variety of control options are available for ThinLine 3G Vertical F
14 Daikin IM 980-1Operation and Maintenance• On-Off fan and On-Off valve cycle operation: Thethermostat cycles the fan from the manually selected fans
Daikin IM 980-1 15Operation and MaintenanceLow-Voltage (LV) Interface BoardThe low-voltage interface board is used with any remote (wall mounted) Daik
16 Daikin IM 980-1Operation and MaintenanceAccessoriesFresh Air DamperThe fresh air damper kit provides up to 25% outside air to the unit heater. It c
Daikin IM 980-1 17Operation and MaintenanceLeveling Legs OptionField or factory-installed kits are available with 0” to 1" adjustment for positiv
18Daikin IM 980-1Operation and MaintenanceKey-lock Access Door KitThe key-lock access door kit (see Figure 26) can be installed on ThinLine 3G cabinet
Daikin IM 980-1 19Operation and MaintenanceAccessing/removing the main drain pan and motor assemblyThe main drain pan is housed in the top of the unit
2 Daikin IM 980-1Table of ContentsIM 980-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3General Information .
20 Daikin IM 980-1Physical DataPhysical DataUnit DataTable 1: Unit DataShipping WeightsTable 2: Approximate Shipping Weights - lbs (kg)* 02 03 04 06 0
Daikin IM 980-1 21Physical DataUnit DimensionsFigure 30: Dimensions: Flat Top Fan CoilsDimensionS02 S03 S04 S06 S08 S10 S12inch mm inch mm inch mm inc
22 Daikin IM 980-1Physical DataFigure 31: Dimensions: Slope Top Fan CoilsDimensionS02 S03 S04 S06 S08 S10 S12inch mm inch mm inch mm inch mm inch mm i
Daikin IM 980-1 23Physical DataFigure 32: Dimensions: Hideaway, Front-Discharge Fan CoilsDimensionS02 S03 S04 S06 S08 S10 S12inch mm inch mm inch mm i
24 Daikin IM 980-1Physical DataFigure 33: Dimensions: Hideaway, Top-Discharge Fan CoilsDimensionS02 S03 S04 S06 S08 S10 S12inch mm inch mm inch mm inc
Daikin IM 980-1 25Physical DataFactory-Installed Valve & Piping PackagesSee catalog CAT 722-1 for detailed descriptions of piping packages.Figure
26 Daikin IM 980-1Wiring DiagramsWiring DiagramsFigure 35: Fan Coil Wiring Diagram - Typical with solid-state thermostatNote: All field installed con
Daikin IM 980-1 27Wiring DiagramsFigure 36: Fan Coil Wiring Diagram - Typical with unit-mounted three-speed fan switchNote: All field installed condu
28 Daikin IM 980-1Wiring DiagramsFigure 37: Fan Coil Wiring Diagram - Typical with electric heat and low-voltage interface boardNote: All field insta
Daikin IM 980-1 29Model Number DescriptionModel Number De scriptionTable 1: Model Number Description: Fields 1 - 211Unit Type•FC = fan coil• FH = cabi
Daikin IM 980-1 3General InformationGeneral InformationThinline™ 3G Vertical Fan Coils are intended for use in single zone applications. They are avai
30 Daikin IM 980-1Model Number DescriptionTable 2: Model Number Description: Fields 21 - 4122Not currently used• YY = none23 Reheat Coil Type• W1 = 1-
Daikin IM 980-1 31Model Number DescriptionTable 3: Model Number Description: Fields 43-5942Network Communication Card• Y = none43 Changeover Type• Y =
32 Daikin IM 980-1Model Number DescriptionTable 5: Model Number Description: Fields 57 - 7257Filter Status Sensor•Y = None• X = special58 Fan Status S
Daikin IM 980-1 33Model Number DescriptionTable 6: Model Number Description: Fields 73 - 7873Special Options• YYY = none74 Reserved for future use• Y
This page intentionally left blank.Daikin IM 980-1
Page 35 © 2011 Daikin 800-432-1342 www.DaikinApplied.comIM 1121 - Hideaway Unit Discharge Conversion KitSafety InformationIntroduction There may be i
36 Daikin IM 1121Figure 1: Removing the Discharge Duct Collar and Front Block-off PlateFigure 2: Attaching the Top Block-Off Plate and Short Front Pan
Page 37 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1023 - Fresh Air Damper KitThe fresh air damper kit provides up to 25% outside air to the
© 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1023/Page 38OperationTo open the damper, reach under the unit and pull the damper handle toward yo
Page 39 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1028 - Fresh Air Damper Motor KitThis damper motor kit is set up for field installation wi
4 Daikin IM 980-1General InformationReceiving and StorageUpon receipt of the equipment, check carton for visible damage. Make a notation on the shippe
© 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1028/Page 404 Install the coupling on the end of the damper pivot rod closest to the unit control
Page 41 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1024 - Cabinet Rear Extension KitThe field-installed cabinet rear extension option may be
© 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1024/Page 423 Attach Subbase Extensions to the Right and Left Chassis Support Panels using 1 screw
Page 43 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1021 - Ke y-Lock Access Door KitThe key-lock access door kit can be installed on ThinLine
This page intentionally left blank.Daikin IM 980-1
Page 45 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1014 - MTA/B 155 Electronic ThermostatsInstallation1 Install the thermostat with the two f
© 2009 Daikin 800-432-1342 www.DaikinApplied.com IM 1014/Page 46for fan continuous operation or is dependant upon connection to the fan supply input .
© 2010 Daikin 800-432-1342 www.DaikinApplied.comIM 1089 - Field Installation of MT155 ThermostatsGeneralInstallationPlease refer to Fig. 1, 2, 3 and 4
Page 48 Daikin IM 1089Figure 2: Low Voltage Interface Board shown with all additional support options Figure 3: Factory-installed and wired Low Voltag
Daikin IM 1089 Page 49Figure 4: Thermostat TB155 autochangeover to be used with On-Off 24V valve packages, SPDT ACO and unit-mountedLow Voltage Interf
Daikin IM 980-1 5General InformationRecommended Maintenance ClearanceCabinet units have removable front and side panels for easy access to components
This page intentionally left blank.Daikin IM 980-1
Installation and Maintenance Manual IM 1015MTA 158 Microprocessor ThermostatOn/Off ControllerGroup: Applied Air SystemsPart Number: 910102990Date: Aug
Page 52 IM 1015Thermostat OperationThese thermostats are designed to control On-Off, N.O. and N.C. valves, relays and Erie® three wire floating valves
IM 1015/Page 53 © 2009 Daikin 800-432-1342 www.DaikinApplied.comFigure 3: Circuit Board JumpersTable 3: Circuit Board Jumper ConfigurationApplication
This page intentionally left blank.DaikinIM 980-1
Page 55 © 2010 Daikin 800-432-1342 www.DaikinApplied.comIM 1016-1 - MTB 158 Microprocessor ThermostatsFigure 1: Wiring Diagram for 3-Wire Valve Conf
Page 56 Daikin IM 1016-12 For wall installations, mount the thermostat on an inside wall approximately 5 feet above the floor. The location should pro
Page 57 © 2010 Daikin 800-432-1342 www.DaikinApplied.comApplication Notes1 When no pipe sensor is used the main output controls cooling and the seco
This page intentionally left blank.Daikin IM 980-1
Page 59 © 2009 Daikin 800-432-1342 www.DaikinApplied.comIM 1017 - MT 168 0-10Vdc/4020mA ThermostatsInstallation1 Install the thermostat with the two
6 Daikin IM 980-1InstallationInstallationUncrating and Inspecting the Unit1 Carefully remove the packaging, remaining alert to any signs of shipping d
Page 60 Daikin IM 10175 Connecting a jumper between terminals 16 and 17 will disable the secondary output and change the main output to heat mode.6 Co
IM 1017/Page 61 © 2009 Daikin 800-432-1342 www.DaikinApplied.comTable 3: Dip Switch ConfigurationNote: * On is with the dip switch handle to the rig
This page intentionally left blank.Daikin IM 980-1
© 2006 Daikin 800-432-1342 www.DaikinApplied.comUSIM 846 - MT 170 ThermostatsInstallation and Maintenance Manual IM-846T170 ThermostatGroup: Fan CoilP
Page 64 Daikin IM 846Table of ContentsTable of ContentsInstallation Instructions. . . . . . . . . . . . . . . . . . . . . . 3Thermostat Model and Part
Daikin IM 846 Page 65Installation InstructionsInstallation InstructionsThermostat Model and Part Number Daikin offers two different thermostats depend
Page 66 Daikin IM 846Installation Instructions5On the circuit board, set the voltage selection switch (Figure 2) to the appropriate voltage for the ap
Daikin IM 846 Page 67OperationOperationThermostat Button OperationThe thermostat interface (Figure 4) contains buttons for use in navigating to accomp
Page 68 Daikin IM 846OperationThermostat Menu FunctionsThe thermostat menu contains nine functions which can be accessed using controls on the thermos
Daikin IM 846 Page 69OperationFan OperationThe thermostat may be factory configured for standard or staged fan operation.Standard Fan Configuration (T
Daikin IM 980-1 7Installationselect the correct fasteners for each unit to meet local codes. At location(s) where no stud is present, secure with a To
Page 70 Daikin IM 846OperationFancoil OperationFancoil operation is either a 2-pipe or 4-pipe configuration which is determined by jumper selection JP
Daikin IM 846 Page 71Optional Occupancy Detection Equipment OperationOptional Occupancy Detection Equipment OperationThe T170 thermostat can be used w
Page 72 Daikin IM 846Optional Occupancy Detection Equipment OperationFigure 10: Optional equipment configuration #1
Daikin IM 846 Page 73Optional Occupancy Detection Equipment OperationSD200-001 Occupancy SensorThe SD200-001 occupancy sensor (Figure 11) serves as a
Page 74 Daikin IM 846Optional Occupancy Detection Equipment OperationSD200-002 Occupancy SensorThe SD200-002 occupancy sensor serves as a stand alone
This page intentionally left blank.Daikin IM 980-1
© 2006 Daikin • www.DaikinApplied.com • 800-432-1342Daikin Training and DevelopmentNow that you have made an investment in modern, efficient Daikin eq
Page 77 © 2011 Daikin 800-432-1342 www.DaikinApplied.comIM 831 - Thermostat Conversion KitSafety InformationIntroduction This thermostat conversion k
© 2011 Daikin 800-432-1342 www.DaikinApplied.com IM 831/Page 78Figure 3: Remove plastic fan slide switch cap Figure 4: Thermostat cover without 3-spee
Page 79 © 2011 Daikin800-432-1342 www.DaikinApplied.comIM 763 - Automatic Changeover SwitchSafety InformationIntroductionThese line voltage chan
8 Daikin IM 980-1Installation11 Do not connect a unit to the supply and return piping until the water system has been cleaned and flushed completely.
© 2011 Daikin 800-432-1342 www.DaikinApplied.com IM 763/Page 80Specifications Figure 2: Automatic Changeover Switch (Kit P/N 061361801) Table 1: Elec
This page intentionally left blank.Daikin IM 980-1
© 2011 Daikin 05/11Daikin Training and DevelopmentNow that you have made an investment in modern, efficient Daikin equipment, its care should be a hig
Daikin IM 980-1 9Installationmain supply line and the fan coil unit. These can be furnished as part of a factory-installed valve & piping package