Design & installation Guide For McQuay MDS Multi System
Reinforcement of the air pipe
Generally, the air pipe is reinforced through using the ridge web and ridge lines, or adding flanges
or reinforcing frames. Strictly follow the newest national standard Ventilation and Air Condition-
ing Engineering and Acceptance Standard when making and installing the pipes.
Accessories of the air system
The air system has following accessories: air outlet/return air inlet, outside rainproof shutter, air
flow adjusting valve, smoke discharge & fireproof valve, and air deflector. The smoke discharge
& fireproof valve must be tested before installed. The surface of the air outlet and the return air
inlet must be smooth and even. The size of the neck part must be within the allowed deviation
range so that it can engage with the air pipe tightly. The entire air conditioning system, including
all the accessories, should be firm and tight, and, after installed, it should be pass the light
leakage or air leakage acceptance check for a low-pressure air pipe system.
Heat insulation of the air system
The heat insulating layer of the air pipe system should also be non-flammable. Generally, it is 25
mm thick if it is PE materials, or at least 35 mm when consisting of common glass cotton. This
layer should be even, dense, closely attached to the air pipe and its accessories, and without cold
bridges. It should also be well protected against scratch.
Design and calculation of fresh air flow
The fresh air volume mainly depends on the health requirements, the supplementary local air exhaust
volume, and therequirement to guarantee the air conditioned room in positive pressure.
Health requirements
Generally, in both the country and the city, the content of carbon dioxide outdoor is 0.50.75 g/
kg. According to the allowed density of this gas (see the following table), you can use the overall
ventilation volume defined in the Industrial Ventilation to calculate the volume of fresh air needed
to eliminate it.
Elbow
The rectangular air pipe can be inner-arc or inner-slanting, as shown in Figure 4-2. When the
longest side is 500 mm or longer, a flow deflector must be used.
Wall thickness of the air pipe
The wall thickness directly relates to the effect and life of the pipe. A too thin wall will cause
unstable installation, and thus the pipe will sway within a large range to increase the noise. Even
worse, the friction might compound the problem, shortening the service life of the air pipe or even
the entire air conditioning system.
Air pipe elbow
320 340450 480630 6701000 11201250 13202000
Low-speed air pipe 0.5 0.6 0.8 1.0 1.2
High-speed air pipe 0.8 0.8 0.8 1.0 1.2
Round air pipe 0.5 0.6 0.8 1.0 1.2
Connection mode Insertion Flange
Unit: mmRecommended thickness of steel air pipes and accessories
Diameter of round air pipe or
length of the longest side of rect-
angular air pipe
Rectangular
air pipe