5 Troubleshooting
If the followings unit malfunction occurred, please follow the below simple checking step to fix :
Symptom analysis Solution
Indoor temperature is higher (heating) or lower (cooling)
than setting temperature
Re – set up the temperature
Compressor stop and fan work
normally
When heating and defrost mode, indoor unit is just running Wait for 10minutes
Power is not on Check and connect the power
Set up the re-start function Wait or cancel timer On
Units do not work
Fuse broken in main power supply Replace the fuse
Air filter is too dirty Clean or replace the filter
Cooling or heating not enough
or too much
Return air barrier Remove the barrier
Low battery Replace the battery
Remote controller
unreadable
Wrong installation of battery Install properly
Humidity is too high Dehumidify
Condensing water in front panel
Setting temperature is too low Set up the higher indoor temperature
If user can not fix the problem, please contact wit the local service agent for assistance, meanwhile record the malfunction code by remote
controller and indication light of units self-checking function.
Item
code
Description
Item
code
Description
Item
code
Description
1
E0
System malfunction 26
FB
Water pump(indoor drain pump) 49
15
Sensor broken(slaveTH5 mid coil 2#)
2
E1
Sensor broken (TH1 discharge
temp.)
27
FC
Indoor&outdoor
communication malfunction
50
16
Sensor broken(slaveTH6 inlet coil 3#)
3
E2
Sensor broken (TH2 inlet coil 1#) 28
FE
Outdoor master and outdoor slave
communication malfunction
51
17
Sensor broken(slaveTH7 mid coil 3#)
4
E3
Sensor broken (TH3 mid coil 1#) 29
FF
Fresh air filter clogging 52
18
Sensor broken(slaveTH8 ambient temp.)
5
E4
Sensor broken (TH4 inlet coil 2#) 30
H0
Digital comp overload 53
19
Sensor broken(slaveTH9 outlet coil)
6
E5
Sensor broken (TH5 mid coil 2#) 31
H1
Fixed comp1 overload 54
1A
Sensor broken (slave TH10 subcool
outlet)
7
E6
Sensor broken (TH6 inlet coil 3#) 32
H2
Fixed comp2 overload 55
1B
Sensor broken ( slave TH11 subcool
suction)
8
E7
Sensor broken (TH7 mid coil 3#) 33
H3
Fixed comp3 overload 56
1C
Sensor broken(slaveTH12 suction)
9
E8
Sensor broken (TH8 ambient temp.)
34
H4
High pressure too high 57
1F
Emergency run(slave)
10
E9
Sensor broken (TH9 outlet coil) 35
H5
Sensor broken, high pressure 58
20
Outdoor storage malfunction(slave)
11
EA
Sensor broken (TH10subcool outlet)
36
H6
Discharge temp too high 59
27
Ambient temp exceed the limit(slave)
12
EB
Sensor
broken (TH11subcool
suction)
37
H7
High pressure too low 60
28
Water temp. too high or low (slave)
13
EC
Sensor broken (TH12suction) 38
L0
Super heat too low 61
29
Insufficient water flow (slave)
14
EF
Emergency run 39
L1
Low pressure too low 62
30
Digital comp overload(slave)
15
F0
Outdoor storage malfunction 40
L2
Sensor broken, low pressure 63
31
Fixed comp1overload(slave)
16
F1
Sensor broken (indoor inlet coil) 41
L3
All indoor units and outdoor units t
communication malfunction
64
32
Fixed comp2 overload(slave)
17
F2
Sensor broken (indoor mid coil) 42
L6
Outdoor unit and elec.
power dist.
communication malfunction
65
33
Fixed comp3 overload(slave)
18
F3
Sensor broken (indoor outlet coil) 43
L7
Ammeter and elec. power dist.
communication malfunction
66
34
High pressure too high(slave)
19
F4
Sensor broken (indoor return air )
The following for the Slave units
67
35
Sensor broken, high pressure(slave)
20
F5
Sensor broken (indoor supply air) 44
10
System malfunction 68
36
Discharge temp too high(slave)
21
F6
Indoor and controller
communication malfunction
45
11
Sensor broken
(slaveTH1 discharge temp.)
69
37
High pressure too low(slave)
22
F7
Ambient temp exceed the limit 46
12
Sensor broken(slaveTH2 inlet coil 1#) 70
40
Super heat too low(slave)
23
F8
Water temp. too high or low 47
13
Sensor broken(slaveTH3 mid coil 1#) 71
41
Low pressure too low(slave)
24
F9
Insufficient water flow 48
14
Sensor broken(slaveTH4 inlet coil 2#) 72
42
Sensor broken, low pressure(slave)
25
FA
Controller storage malfunction
Indication light twinkle related to the code of malfunction:
Type Heat
Sleep/Fan
Dry
Type Heat
Sleep/Fan
Dry
Type Heat Sleep/Fan
Dry
Sensor , indoor Off
Off F
Sensor, outdoor Off
F F
Pressure sensor,
outdoor
F F On
Pump , indoor Off
F Off
Overload , compressor
F F Off System failure F F F
Communication F Off Off
Pressure high/low F Off F Others F On On
Note : “ F” means “ flash” , “ On” means “ light on” , “ Off” means “ light off”