Design & installation Guide For McQuay MDS Multi System
Description of controller hardware
Input port:
The system contains 5 test ports designed for high/low pressure test, digital compressor
overload, constant speed compressor overload 1 and constant speed compressor overload 2
(used when 3 compressors are available)
Output port:
The system contains 9 output control ports including PWM valve, 4-way valve, digital compres-
sor/constant-speed compressor main power supply, high/medium/low wind, SI (reserved as the
main power supply for the second constant-speed compressor of the 3 compressor systems, if
applicable) and riving port for electronic expansion valve.
Sensor test port
The system has 7 temperature test ports designed to test the temperature of the digital
compressor exhaust, ambient temperature, return-air temperature, the bottom temperature of
compressor, inlet temperature, midlet temperature and outlet temperature (Note: The flow
direction of the refrigerant inside the coils when the system is running in cooling mode determines
the inflow and outflow direction described in this document).
Communication port:
The system has two RS485 communication ports. One network with the indoor units and the
other is used for internetworking control.
DIP switch setting
J1 settings (1:ON: 0:OFF)
J1.1 J1.2
Initial opening extent
J1.1 J1.2
Initial opening extent
of the expansion valve of the expansion valve
00 300 1 0 400
01 350 1 1 450
J1.3 reserved
J1.4: J1.5: J1.6: J1.7 capacity settings
Note: Other DIP switches are reserved.
No. J1.4 J1.5 J1.6 J1.7 Capacity
10 00010.0kW/4HP
20 00112.5kW/5HP
30 01015.0kW/6HP
40 01122.5kW/8HP
50 10028.1kW/10HP
60 1 01 3HP